Protecting Settings From Unauthorized; Access - Endress+Hauser Proline Prosonic Flow E 100 HART Operating Instructions Manual

Ultrasonic time-of-flight flowmeter
Table of Contents

Advertisement

Proline Prosonic Flow E 100 HART
Parameter
Value current output 1
Frequency output simulation 1
Frequency value 1
Pulse output simulation 1
Pulse value 1
Switch output simulation 1
Switch status 1
Device alarm simulation
Diagnostic event category
Diagnostic event simulation
*
Visibility depends on order options or device settings
Endress+Hauser
Prerequisite
In the Current output
simulation parameter, the On
option is selected.
In the Operating mode
parameter, the Frequency
option is selected.
In the Frequency output
simulation parameter, the On
option is selected.
In the Operating mode
parameter, the Pulse option is
selected.
In the Pulse output
simulation parameter
(→  65), the Down-
counting value option is
selected.
In the Operating mode
parameter, the Switch option
is selected.
In the Switch output
simulation parameter
(→  65) Switch output
simulation 1 to n parameter
Switch output simulation
1 to n parameter, the On
option is selected.
10.7
Protecting settings from unauthorized access
The following options exist for protecting the configuration of the measuring device from
unintentional modification after commissioning:
• Write protection via access code for Web browser
• Write protection via write protection switch →  66
Description
Enter the current value for
simulation.
Switch the simulation of the
frequency output on and off.
Enter the frequency value for
the simulation.
Set and switch off the pulse
output simulation.
For Fixed value option:
Pulse width parameter
(→  49) defines the
pulse width of the pulses
output.
Enter the number of pulses for
simulation.
Switch the simulation of the
switch output on and off.
Select the status of the status
output for the simulation.
Switch the device alarm on and
off.
Select a diagnostic event
category.
Select a diagnostic event to
simulate this event.
Commissioning
Selection / User
Factory setting
entry
3.59 to 22.5 mA
3.59 mA
• Off
Off
• On
0.0 to 12 500.0 Hz
0.0 Hz
• Off
Off
• Fixed value
• Down-counting
value
0 to 65 535
0
• Off
Off
• On
• Open
Open
• Closed
• Off
Off
• On
• Sensor
Process
• Electronics
• Configuration
• Process
• Off
Off
• Diagnostic event
picklist (depends
on the category
selected)
65