Configuring The Low Flow Cut Off - Endress+Hauser Proline Prosonic Flow E 100 HART Operating Instructions Manual

Ultrasonic time-of-flight flowmeter
Table of Contents

Advertisement

Commissioning
Parameter
Assign process variable
On value low flow cutoff
Off value low flow cutoff
56
10.4.6

Configuring the low flow cut off

The Low flow cut off submenu contains the parameters that must be set in order to
configure the low flow cut off.
Structure of the wizard
 13
"Low flow cutoff" wizard in the "Setup" menu
Navigation
"Setup" menu → Low flow cut off
Low flow cut off
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Parameter overview with brief description
Prerequisite
In the Assign process variable
parameter (→  56), one of
the following options is
selected:
• Volume flow
• Mass flow
In the Assign process variable
parameter (→  56), one of
the following options is
selected:
• Volume flow
• Mass flow
Assign variable
Off
Volume flow
On value
Off value
End of wizard
Description
Select process variable for low
flow cut off.
Enter on value for low flow cut
off.
Enter off value for low flow cut
off.
Proline Prosonic Flow E 100 HART
Mass flow
→  56
→  56
→  56
Selection / User
Factory setting
entry
• Off
Off
• Volume flow
• Mass flow
Positive floating-
Depends on country
point number
and nominal
diameter
0 to 100.0 %
50 %
Endress+Hauser
A0034560-EN