Products Solutions Services BA01712D/06/EN/04.24-00 71675038 2024-11-01 Valid as of version 01.02.zz (Device firmware) Operating Instructions Proline Promass E 100 Coriolis flowmeter EtherNet/IP...
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser sales organization will supply you with current information and updates to this manual. Endress+Hauser...
Page 3
Proline Promass E 100 EtherNet/IP Table of contents Table of contents 6.2.3 Mounting the measuring device ..23 About this document ....6 Post-installation check .
Page 4
13.2 Measuring and test equipment ... 108 13.3 Endress+Hauser services ....108 Operation ......71 Repair .
Page 5
Proline Promass E 100 EtherNet/IP Table of contents 16.5 Power supply ......120 16.6 Performance characteristics ... . . 121 16.7 Mounting .
Page 6
About this document Proline Promass E 100 EtherNet/IP About this document Document function These Operating Instructions contain all the information required in the various life cycle phases of the device: from product identification, incoming acceptance and storage, to installation, connection, operation and commissioning, through to troubleshooting, maintenance and disposal.
Page 7
For an overview of the scope of the associated Technical Documentation, refer to the following: • Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the nameplate • Endress+Hauser Operations app: Enter serial number from nameplate or scan matrix code on nameplate. Endress+Hauser...
Page 8
About this document Proline Promass E 100 EtherNet/IP The following documentation may be available depending on the device version ordered: Document type Purpose and content of the document Technical Information (TI) Planning aid for your device The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
Page 9
Proline Promass E 100 EtherNet/IP Safety instructions Safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
Page 10
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
Page 11
Proline Promass E 100 EtherNet/IP Safety instructions IT security Our warranty is valid only if the product is installed and used as described in the Operating Instructions. The product is equipped with security mechanisms to protect it against any inadvertent changes to the settings.
Page 12
Product description Proline Promass E 100 EtherNet/IP Product description The device consists of a transmitter and a sensor. The device is available as a compact version: The transmitter and sensor form a mechanical unit. Product design 3.1.1 Device version with EtherNet/IP communication protocol A0023153 ...
Page 13
• Enter the serial numbers from the nameplates in the Device Viewer (www.endress.com/deviceviewer): all the information about the device is displayed. • Enter the serial numbers from the nameplates into the Endress+Hauser Operations app or scan the DataMatrix code on the nameplate with the Endress+Hauser Operations app: all the information about the device is displayed.
Page 14
Incoming acceptance and product identification Proline Promass E 100 EtherNet/IP 4.2.1 Transmitter nameplate Order code: Ser. no.: Ext. ord. cd.: A0030222 2 Example of a transmitter nameplate Manufacturer address/certificate holder Name of the transmitter Order code Serial number Extended order code Electrical connection data, e.g.
Page 15
Proline Promass E 100 EtherNet/IP Incoming acceptance and product identification Date: A0029207 4 Example of a sensor nameplate, part 2 Approval information for explosion protection, Pressure Equipment Directive and degree of protection Allowable ambient temperature (T Document number of safety-related supplementary documentation...
Page 16
Storage and transport Proline Promass E 100 EtherNet/IP Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
Page 17
Proline Promass E 100 EtherNet/IP Storage and transport 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device. ‣...
Page 18
Installation Proline Promass E 100 EtherNet/IP Installation Installation requirements 6.1.1 Installation position Installation point A0028772 To prevent measuring errors arising from accumulation of gas bubbles in the measuring pipe, avoid the following mounting locations in the piping: • Highest point of a pipeline.
Page 19
Proline Promass E 100 EtherNet/IP Installation Ø orifice plate, pipe restriction [mm] [in] [mm] [in] ³⁄₈ 0.24 ½ 0.40 0.55 1 ½ 0.87 1.10 1.97 Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction (direction of medium flow through the piping).
Page 20
Installation Proline Promass E 100 EtherNet/IP Inlet and outlet runs No special precautions need to be taken for fittings that create turbulence, such as valves, elbows or T-pieces, as long as no cavitation occurs → 20. A0029322 A0029323 Installation dimensions For the dimensions and installation lengths of the device, see the "Technical...
Page 21
Proline Promass E 100 EtherNet/IP Installation NOTICE Electronics overheating on account of thermal insulation! ‣ Recommended orientation: horizontal orientation, transmitter housing pointing downwards. ‣ Do not insulate the transmitter housing . ‣ Maximum permissible temperature at the lower end of the transmitter housing: 80 °C (176 °F)
Page 22
Installation Proline Promass E 100 EtherNet/IP 6.1.3 Special installation instructions Drainability When installed vertically, the measuring tubes can be drained completely and protected against buildup. Hygienic compatibility When installing in hygienic applications, please refer to the information in the "Certificates and approvals/hygienic compatibility" section → 133 Rupture disk Process-related information: →...
Page 23
Proline Promass E 100 EtherNet/IP Installation To get a representative zero point, ensure that: • any flow in the device is prevented during the adjustment • the process conditions (e.g. pressure, temperature) are stable and representative Verification and adjustment cannot be carried out if the following process conditions are present: •...
Page 24
Installation Proline Promass E 100 EtherNet/IP 2. Install the measuring device or turn the transmitter housing so that the cable entries do not point upwards. A0029263 Post-installation check Is the device undamaged (visual inspection)? Does the measuring instrument correspond to the measuring point specifications? For example: •...
Page 25
Proline Promass E 100 EtherNet/IP Electrical connection Electrical connection WARNING Live parts! Incorrect work performed on the electrical connections can result in an electric shock. ‣ Set up a disconnecting device (switch or power-circuit breaker) to easily disconnect the device from the supply voltage.
Page 26
Electrical connection Proline Promass E 100 EtherNet/IP 7.2.3 Terminal assignment Transmitter EtherNet/IP connection version Order code for "Output", option N Depending on the housing version, the transmitters can be ordered with terminals or device plugs. Connection methods available Order code...
Page 27
Proline Promass E 100 EtherNet/IP Electrical connection 7.2.4 Pin assignment, device plug Supply voltage Assignment DC 24 V Not assigned Not assigned DC 24 V Grounding/shielding A0016809 Coding Plug/socket Plug Device plug for signal transmission (device side) Assignment Coding Plug/socket...
Page 28
Electrical connection Proline Promass E 100 EtherNet/IP 7.3.1 Connecting the transmitter The connection of the transmitter depends on the following order codes: • Housing version: compact or ultra-compact • Connection version: device plug or terminals A0016924 9 Housing versions and connection versions...
Page 29
Proline Promass E 100 EtherNet/IP Electrical connection For device version with device plug: follow step 6 only. 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover and disconnect the local display from the main electronics module where necessary →...
Page 30
Electrical connection Proline Promass E 100 EtherNet/IP Special connection instructions 7.5.1 Connection examples EtherNet/IP A0028767 11 Connection example for EtherNet/IP Control system (e.g. PLC) Ethernet switch Observe cable specifications Device plug Transmitter Hardware settings 7.6.1 Setting the device address EtherNet/IP The IP address of the measuring device can be configured for the network via DIP switches.
Page 31
Proline Promass E 100 EtherNet/IP Electrical connection Setting the address OFF ON - Write protection - Default Ethernet network settings IP 192.168.1.212 A0017913 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover.
Page 32
Electrical connection Proline Promass E 100 EtherNet/IP Post-connection check Are the device and cable undamaged (visual inspection)? Do the cables used comply with the requirements → 25? Are the installed cables strain-relieved and securely routed? Are all cable glands installed, securely tightened and leak-tight? Cable run with "water trap"...
Page 33
Proline Promass E 100 EtherNet/IP Operation options Operation options Overview of operation options A0017760 Computer with web browser or with "FieldCare" operating tool Automation system, e.g. "RSLogix" (Rockwell Automation) and work station for measuring instrument operation with Add-on Profile Level 3 for "RSLogix 5000" software (Rockwell Automation)
Page 34
Operation options Proline Promass E 100 EtherNet/IP Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: see the "Description of Device Parameters" document supplied with the device → 136...
Page 35
Proline Promass E 100 EtherNet/IP Operation options 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (e.g. operator, maintenance etc.). Each user role contains typical tasks within the device life cycle. Menu/parameter User role and tasks...
Page 36
Operation options Proline Promass E 100 EtherNet/IP Displaying the measured values via the local display (optionally available) 8.3.1 Operational display The local display is optionally available: Order code for "Display; operation", option B ""4-line, illuminated; via communication". X X X X X X X 1120.50...
Page 37
Proline Promass E 100 EtherNet/IP Operation options • Density • Reference density Temperature Totalizer The measurement channel number indicates which of the three totalizers is displayed. Output Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The measurement channel number is displayed only if more than one channel is present for the same measured variable type (e.g.
Page 38
Operation options Proline Promass E 100 EtherNet/IP Access authorization to parameters: "Operator" user role Access code status Read access Write access After an access code has been defined. – Despite the defined access code, certain parameters can always be modified and thus are excluded from the write protection as they do not affect the measurement: write protection via access code The user role with which the user is currently logged on is indicated by the .
Page 39
Proline Promass E 100 EtherNet/IP Operation options Computer settings User rights Appropriate user rights (e.g. administrator rights) for TCP/IP and proxy server settings are necessary (for adjusting the IP address, subnet mask etc.). Proxy server settings of the The web browser setting Use a Proxy Server for Your LAN must be deselected .
Page 40
Operation options Proline Promass E 100 EtherNet/IP 8.4.3 Connecting the device Via service interface (CDI-RJ45) Preparing the measuring device Configuring the Internet protocol of the computer The IP address can be assigned to the measuring device in a variety of ways: •...
Page 41
Proline Promass E 100 EtherNet/IP Operation options 2. Enter the IP address of the web server in the address line of the web browser: 192.168.1.212 The login page appears. 2 3 4 Device name: Device tag: Signal Status: Web server language...
Page 42
Operation options Proline Promass E 100 EtherNet/IP 8.4.5 User interface A0032879 Picture of device Device name Device tag Status signal Current measured values Navigation area Local display language Header The following information appears in the header: • Device name • Device tag •...
Page 43
Proline Promass E 100 EtherNet/IP Operation options Functions Meaning Configuration and checking of all the parameters required for establishing the connection to the measuring device: Network • Network settings (e.g. IP address, MAC address) • Device information (e.g. serial number, firmware version)
Page 44
Operation options Proline Promass E 100 EtherNet/IP 1. Select the Logout entry in the function row. The home page with the Login box appears. 2. Close the Web browser. 3. If no longer needed: Reset the modified properties of the Internet protocol (TCP/IP) → 40.
Page 45
FieldCare Function range FDT-based (Field Device Technology) plant asset management tool from Endress+Hauser. It can configure all smart field units in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
Page 46
DeviceCare Function range Tool for connecting and configuring Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated "DeviceCare" tool. Together with the device type managers (DTMs) it presents a convenient, comprehensive solution. Innovation brochure IN01047S Source for device description files →...
Page 47
Proline Promass E 100 EtherNet/IP System integration System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.02.zz • On the title page of the manual • On the transmitter nameplate • Firmware version Diagnostics →...
Page 48
System integration Proline Promass E 100 EtherNet/IP Integrating the measuring device in the system For detailed information on system integration, see the Operating Instructions for the device A detailed description of how to integrate the device into an automation system (e.g.
Page 49
Proline Promass E 100 EtherNet/IP System integration Configuration 4: Input Only Multicast Input Assembly Configurable Instance Size (byte) Min. RPI (ms) Input Assembly Configurable Configuration 0 x 68 – Output Assembly Fix O → T Configuration 0 x C7 –...
Page 50
System integration Proline Promass E 100 EtherNet/IP Name Description Byte 10. Totalizer 2 37…40 11. Totalizer 3 41…44 Structure: Code, number, description (e.g.: 16777265 F882 input signal) Detailed description: • Diagnostic information → 91 • Information events → 104...
Page 51
Proline Promass E 100 EtherNet/IP System integration Name Description (format) Byte Value 9. Not used 2…4 0…8 – 10. Control totalizer 1 (integer) 5…6 0…8 • -32226: Add • -32490: Reset and stop • -32228: Default value and stop • 198: Reset and add •...
Page 52
Commissioning Proline Promass E 100 EtherNet/IP Commissioning 10.1 Post-mounting and post-connection check Before commissioning the device: ‣ Make sure that the post-installation and post-connection checks have been performed successfully. • Checklist for "Post-installation" check→ 24 • Checklist for "Post-connection" check→ 32 10.2...
Page 53
Proline Promass E 100 EtherNet/IP Commissioning ‣ Partially filled pipe detection → 60 ‣ Advanced setup → 61 10.4.1 Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
Page 54
Commissioning Proline Promass E 100 EtherNet/IP Temperature unit → 55 Pressure unit → 55 Parameter overview with brief description Parameter Description Selection Factory setting Mass flow unit Select mass flow unit. Unit choose list Country-specific: • kg/h Effect •...
Page 55
Proline Promass E 100 EtherNet/IP Commissioning Parameter Description Selection Factory setting Temperature unit Select temperature unit. Unit choose list Country-specific: • °C Effect • °F The selected unit applies to: • Electronic temperature parameter (6053) • Maximum value parameter (6051) •...
Page 56
Commissioning Proline Promass E 100 EtherNet/IP 10.4.3 Selecting and setting the medium The Select medium wizard submenu contains parameters that must be configured in order to select and set the medium. Navigation "Setup" menu → Medium selection ‣ Medium selection Select medium →...
Page 57
Proline Promass E 100 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User entry Reference sound velocity In the Select gas type parameter, the Enter sound velocity of gas at 0 °C (32 1 to 99 999.9999 m/s Others option is selected. °F).
Page 58
Commissioning Proline Promass E 100 EtherNet/IP Parameter Description User interface / Selection / Factory setting User entry DHCP client Select to activate/deactivate DHCP client • Off functionality. • On Effect If the DHCP client functionality of the web server is selected, the IP address, Subnet mask and Default gateway are set automatically.
Page 59
Proline Promass E 100 EtherNet/IP Commissioning 10.4.5 Configuring the low flow cut off The Low flow cut off submenu contains the parameters that must be set in order to configure the low flow cut off. Navigation "Setup" menu → Low flow cut off ‣...
Page 60
Commissioning Proline Promass E 100 EtherNet/IP 10.4.6 Configuring partially filled pipe detection The Partially filled pipe detection submenu contains parameters that have to be set for configuring empty pipe detection. Navigation "Setup" menu → Partially filled pipe detection ‣ Partially filled pipe detection Assign process variable →...
Page 61
Proline Promass E 100 EtherNet/IP Commissioning 10.5 Advanced settings The Advanced setup submenu with its submenus contains parameters for specific settings. The number of submenus can vary depending on the device version, e.g. viscosity is available only with the Promass I.
Page 63
Proline Promass E 100 EtherNet/IP Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Reference temperature The Calculated reference Enter reference temperature –273.15 to 99 999 °C Country-specific: density option is selected in for calculating the reference • +20 °C the Corrected volume flow density.
Page 64
Commissioning Proline Promass E 100 EtherNet/IP Performing density adjustment Note the following before performing the adjustment: • A density adjustment only makes sense if there is little variation in the operating conditions and the density adjustment is performed under the operating conditions.
Page 65
Proline Promass E 100 EtherNet/IP Commissioning 4. Select the Measure density 1 option and confirm. In the Execute density adjustment parameter the following options are now available: Measure density 2 Restore original 5. Select the Measure density 2 option and confirm.
Page 66
Commissioning Proline Promass E 100 EtherNet/IP Parameter Prerequisite Description Selection / User Factory setting entry / User interface Density setpoint 2 In the Density adjustment The entry depends on – mode parameter, the 2 point the unit selected in adjustment option is selected. the Density unit parameter (0555).
Page 67
Proline Promass E 100 EtherNet/IP Commissioning Navigation "Setup" menu → Advanced setup → Sensor adjustment → Zero point adjustment ‣ Zero point adjustment Zero point adjustment control → 67 Progress → 67 Parameter overview with brief description Parameter Description Selection / User interface...
Page 68
Commissioning Proline Promass E 100 EtherNet/IP Parameter Prerequisite Description Selection Factory setting Totalizer operation mode A process variable is selected Select totalizer calculation • Net flow total – in the Assign process variable mode. • Forward flow total parameter (→ 67) of the •...
Page 69
Proline Promass E 100 EtherNet/IP Commissioning Simulation device alarm → 69 Simulation diagnostic event → 69 Parameter overview with brief description Parameter Prerequisite Description Selection / User entry Assign simulation process variable – Select a process variable for the • Off simulation process that is activated.
Page 70
Commissioning Proline Promass E 100 EtherNet/IP Defining the access code via the web browser 1. Navigate to the Define access code parameter. 2. Define a 16-digit (max.) numeric code as the access code. 3. Enter the access code again in the to confirm.
Page 71
Proline Promass E 100 EtherNet/IP Operation Operation 11.1 Read out and modify current Ethernet settings If the Ethernet settings such as the IP address of the measuring device are unknown, they can be read out and modified as explained in the following example for an IP address.
Page 72
Operation Proline Promass E 100 EtherNet/IP Navigation "Operation" menu → Locking status Function scope of "Locking status" parameter Options Description Hardware locked The write protection switch (DIP switch) for hardware locking is activated on the I/O electronic module. This prevents write access to the parameters .
Page 73
Proline Promass E 100 EtherNet/IP Operation Corrected volume flow → 75 → 75 Density Reference density → 75 Temperature → 75 Pressure → 75 Concentration → 75 Target mass flow → 75 Carrier mass flow →...
Page 74
Operation Proline Promass E 100 EtherNet/IP Water CTL → 78 CTL alternative → 79 → 79 CPL alternative CTPL alternative → 79 Oil reference density → 79 Water reference density → 79 → 80...
Page 75
Proline Promass E 100 EtherNet/IP Operation Parameter Prerequisite Description User interface Factory setting Corrected volume flow – Displays the corrected volume Signed floating-point – flow that is currently number calculated. Dependency The unit is taken from: Corrected volume flow unit parameter (→...
Page 76
Operation Proline Promass E 100 EtherNet/IP Parameter Prerequisite Description User interface Factory setting Carrier corrected volume flow – Signed floating-point – number Target volume flow – Signed floating-point – number Carrier volume flow – Signed floating-point – number For the following order code:...
Page 77
Proline Promass E 100 EtherNet/IP Operation Parameter Prerequisite Description User interface Factory setting S&W correction value For the following order code: Shows the correction value for Positive floating- – • "Application package", option sediment and water. point number EJ "Petroleum"...
Page 78
Operation Proline Promass E 100 EtherNet/IP Parameter Prerequisite Description User interface Factory setting NSV flow alternative For the following order code: Displays the net volume flow Signed floating-point – • "Application package", option which is calculated from the number EJ "Petroleum"...
Page 79
Proline Promass E 100 EtherNet/IP Operation Parameter Prerequisite Description User interface Factory setting CTL alternative For the following order code: Displays the correction factor Positive floating- – • "Application package", option which represents the effect of point number EJ "Petroleum"...
Page 80
Operation Proline Promass E 100 EtherNet/IP Parameter Prerequisite Description User interface Factory setting Oil density For the following order code: Displays the density of the oil Signed floating-point – • "Application package", option currently measured. number EJ "Petroleum" • In the Petroleum mode parameter, the Net oil &...
Page 81
Proline Promass E 100 EtherNet/IP Operation Parameter Prerequisite Description User interface Factory setting Oil mass flow For the following order code: Displays the currently Signed floating-point – • "Application package", option calculated mass flow of the oil. number EJ "Petroleum"...
Page 82
Operation Proline Promass E 100 EtherNet/IP Parameter Prerequisite Description User interface Factory setting Weighted density average For the following order code: Displays the weighted average Signed floating-point – • "Application package", option for the density since the last number EJ "Petroleum"...
Page 83
Proline Promass E 100 EtherNet/IP Operation Parameter overview with brief description Parameter Prerequisite Description User interface Totalizer value 1 to n One of the following options is selected Displays the current totalizer counter Signed floating-point in the Assign process variable value.
Page 84
Operation Proline Promass E 100 EtherNet/IP Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry / User interface Control Totalizer 1 to n A process variable is selected Control totalizer value. • Totalize – in the Assign process variable •...
Page 85
Proline Promass E 100 EtherNet/IP Operation Parameter Prerequisite Description Selection / User Factory setting entry / User interface Reset weighted averages The values can only be reset at Resets the weighted averages • Totalize – zero flow. for density and temperature to • Preset + totalize...
Page 86
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting 12.1 General troubleshooting For local display Error Possible causes Remedial action Local display is dark, but signal output is within The cable of the display module is not plugged in...
Page 87
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Fault Possible causes Remedial action ‣ Unable to connect to the web server. • The IP address on the PC is incorrectly If addressing via hardware: open the configured. transmitter and check the IP address •...
Page 88
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Color Meaning Device status Green Device status is ok Flashing red A device error of diagnostic behavior "Warning" has occurred A device error of diagnostic behavior "Alarm" has occurred Alternately flashing red/green Boot loader is active...
Page 89
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Symbol Meaning Out of specification The device is being operated: Outside its technical specification limits (e.g. outside the process temperature range) Maintenance required Maintenance is required. The measured value remains valid. The status signals are categorized in accordance with VDI/VDE 2650 and NAMUR Recommendation NE 107.
Page 90
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Xxxxxx/…/…/ Device name: Xxxxxxx Mass flow: kg/h 12.34 Device tag: Xxxxxxx Volume flow: 12.34 m /h ³ Status signal: Function check (C) Xxxxxx Diagnostics 1: C485 Simu... Remedy information: Deactivate... Failure (F)
Page 91
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting 2. On the right in the working area, mouse over the parameter. A tool tip with remedy information for the diagnostic event appears. 12.5 Diagnostic information via communication interface 12.5.1 Reading out diagnostic information...
Page 92
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP 12.7.1 Diagnostic of sensor Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 022 Sensor temperature 1. Change main electronic module • 0x10000BE 2. Change sensor • 0x10000BF • 0x10000D5 Status signal •...
Page 93
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 144 Measuring error too high 1. Check process conditions 0x10001C7 2. Check or change sensor Status signal Diagnostic behavior Alarm Diagnostic information...
Page 94
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 252 Modules incompatible 1. Check electronic modules 0x100006B 2. Change electronic modules Status signal Diagnostic behavior Alarm Diagnostic information Remedy instructions...
Page 95
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 274 Main electronic failure Change electronic • 0x80000CE • 0x80000CF Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions Coding of diagnostic...
Page 96
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 390 Special event 2 Contact service 0x1000112 Status signal Diagnostic behavior Alarm Diagnostic information Remedy instructions Coding of diagnostic information (hex)
Page 97
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 438 Dataset 1. Check data set file 0x400006A 2. Check device configuration 3. Up- and download new Status signal configuration Diagnostic behavior...
Page 98
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 590 Special event 3 Contact service 0x1000124 Status signal Diagnostic behavior Alarm Diagnostic information Remedy instructions Coding of diagnostic information (hex)
Page 99
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 831 Sensor temperature too low Increase ambient temp. around the 0x80000C2 sensor housing Status signal Diagnostic behavior Warning Diagnostic information Remedy instructions...
Page 100
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 842 Process limit Low flow cut off active! 0x8000091 1. Check low flow cut off configuration Status signal Diagnostic behavior Warning...
Page 101
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 912 Inhomogeneous 1. Check process cond. • 0x8000115 2. Increase system pressure • 0x8000162 Status signal Diagnostic behavior Warning Diagnostic information...
Page 102
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Diagnostic information Remedy instructions Coding of diagnostic information (hex) Short text 992 Special event 12 Contact service 0x100011F Status signal Diagnostic behavior [from the Alarm factory] Diagnostic behavior can be changed. 12.8...
Page 103
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Parameter Prerequisite Description User interface Operating time from restart – Shows the time the device has been in Days (d), hours (h), operation since the last device restart. minutes (m) and seconds Operating time –...
Page 104
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP Filter categories • All • Failure (F) • Function check (C) • Out of specification (S) • Maintenance required (M) • Information (I) 12.10.3 Overview of information events Unlike a diagnostic event, an information event is displayed in the event logbook only and not in the diagnostic list.
Page 105
Proline Promass E 100 EtherNet/IP Diagnostics and troubleshooting Info number Info name I1459 Failed: I/O module verification I1460 Failed: Sensor integrity verification I1461 Failed: Sensor verification I1462 Failed:Sensor electronic module verific. 12.11 Resetting the measuring device The entire device configuration or some of the configuration can be reset to a defined state with the Device reset parameter (→...
Page 106
Diagnostics and troubleshooting Proline Promass E 100 EtherNet/IP ENP version → 106 IP address Subnet mask Default gateway Parameter overview with brief description Parameter Description User interface Factory setting Device tag Shows name of measuring point. Max. 32 characters, such as –...
Page 107
"Manufacturer' s information" document. The manufacturer' s information is available: • In the Download Area of the Endress+Hauser web site: www.endress.com → Downloads • Specify the following details: •...
Page 108
• Observe the maximum permitted medium temperature for the measuring device . 13.2 Measuring and test equipment Endress+Hauser offers a variety of measuring and testing equipment, such as Netilion or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services.
Page 109
• The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
Page 110
Repair Proline Promass E 100 EtherNet/IP 14.5 Disposal If required by the Directive 2012/19/EU on waste electrical and electronic equipment (WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this marking as unsorted municipal waste.
Page 111
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Page 112
Via the Internet: https://portal.endress.com/webapp/applicator Netilion lloT ecosystem: Unlock knowledge With the Netilion IIoT ecosystem,Endress+Hauser allows you to optimize your plant performance, digitize workflows, share knowledge, and enhance collaboration. Drawing upon decades of experience in process automation, Endress+Hauser offers the process industry an IIoT ecosystem designed to effortlessly extract insights from data.
Page 113
Proline Promass E 100 EtherNet/IP Accessories 15.4 System components Accessories Description Memograph M graphic The Memograph M graphic data manager provides information on all the relevant data manager measured variables. Measured values are recorded correctly, limit values are monitored and measuring points analyzed. The data are stored in the 256 MB internal memory and also on a SD card or USB stick.
Page 114
Technical data Proline Promass E 100 EtherNet/IP Technical data 16.1 Application The measuring device is intended only for the flow measurement of liquids and gases. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
Page 115
Proline Promass E 100 EtherNet/IP Technical data 16.3 Input Measured variable Direct measured variables • Mass flow • Density • Temperature Calculated measured variables • Volume flow • Corrected volume flow • Reference density Measuring range Measuring range for liquids Measuring range full scale values ...
Page 116
• Operating pressure to increase measurement accuracy (Endress+Hauser recommends the use of a pressure measuring instrument for absolute pressure, e.g. Cerabar M or Cerabar S) •...
Page 117
Proline Promass E 100 EtherNet/IP Technical data Local display Plain text display With information on cause and remedial measures Backlight Red backlighting indicates a device error. Status signal as per NAMUR recommendation NE 107 Interface/protocol • Via digital communication: EtherNet/IP •...
Page 118
Technical data Proline Promass E 100 EtherNet/IP I/O connections Max. 6 connections (scanner) Configuration options for • DIP switches on the electronics module for IP addressing measuring instrument • Manufacturer-specific software (FieldCare) • Add-on Profile Level 3 for Rockwell Automation control systems •...
Page 119
Proline Promass E 100 EtherNet/IP Technical data O → T configuration: 0x66 T → O configuration: 0x65 Input only Multicast Instance Size [byte] Instance configuration: 0x68 O → T configuration: 0xC7 T → O configuration: 0x65 Input only Multicast Instance...
Page 120
Technical data Proline Promass E 100 EtherNet/IP 16.5 Power supply Terminal assignment • → 26 • Available device plugs • • → 27 • • • Supply voltage The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).
Page 121
Proline Promass E 100 EtherNet/IP Technical data Cable specification → 25 16.6 Performance characteristics Reference operating • Error limits based on ISO 11631 conditions • Water • +15 to +45 °C (+59 to +113 °F) • 2 to 6 bar (29 to 87 psi) •...
Page 123
Proline Promass E 100 EtherNet/IP Technical data Influence of medium Mass flow temperature o.f.s. = of full scale value If there is a difference between the temperature during zero adjustment and the process temperature, the additional measurement error of the sensors is typically ±0.0002 %o.f.s./°C (±0.0001 % o.
Page 124
Technical data Proline Promass E 100 EtherNet/IP Design fundamentals o.r. = of reading, o.f.s. = of full scale value BaseAccu = base accuracy in % o.r., BaseRepeat = base repeatability in % o.r. MeasValue = measured value; ZeroPoint = zero point stability...
Page 125
Proline Promass E 100 EtherNet/IP Technical data Temperature tables Observe the interdependencies between the permitted ambient and fluid temperatures when operating the device in hazardous areas. For detailed information on the temperature tables, see the separate document entitled "Safety Instructions" (XA) for the device.
Page 126
Technical data Proline Promass E 100 EtherNet/IP Pressure-temperature For an overview of the pressure-temperature ratings for the process connections, see ratings the Technical Information Sensor housing The sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside.
Page 127
Proline Promass E 100 EtherNet/IP Technical data • The minimum recommended full scale value is approx. 1/20 of the maximum full scale value • In most applications, 20 to 50 % of the maximum full scale value can be considered ideal •...
Page 128
Technical data Proline Promass E 100 EtherNet/IP 16.10 Mechanical construction Design, dimensions For the dimensions and installation lengths of the device, see the "Technical Information" document, "Mechanical construction" section Weight All values (weight exclusive of packaging material) refer to devices with EN/DIN PN 40 flanges.
Page 129
Proline Promass E 100 EtherNet/IP Technical data Cable entries/cable glands A0020640 16 Possible cable entries/cable glands Female thread M20 × 1.5 Cable gland M20 × 1.5 Adapter for cable entry with female thread G ½" or NPT ½" Order code for "Housing", option A "Compact, aluminum, coated"...
Page 130
Technical data Proline Promass E 100 EtherNet/IP Process connections • Flanges according to EN 1092-1 (DIN2501) / according to ASME B 16.5 / as per JIS B2220: Stainless steel, 1.4404 (F316/F316L) • All other process connections: Stainless steel, 1.4404 (316/316L) Available process connections→...
Page 131
Proline Promass E 100 EtherNet/IP Technical data Category Method Option(s) order code "Measuring tube mat., wetted surface" Ra ≤ 0.38 µm (15 µin) Mechanically polished Ra ≤ 0.38 µm (15 µin) Mechanically polished , welds in as-welded condition Ra according to ISO 21920 Except for inaccessible welds between pipe and manifold 16.11 Operability...
Page 132
Technical data Proline Promass E 100 EtherNet/IP Star topology A0032078 17 Options for remote operation via EtherNet/IP network: star topology Automation system, e.g. "RSLogix" (Rockwell Automation) Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell Automation) or with Electronic Data Sheet (EDS) Computer with Web browser (e.g.
Page 133
The device meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. UKCA marking The device meets the legal requirements of the applicable UK regulations (Statutory Instruments).
Page 134
Directive a) PED/G1/x (x = category) or b) PESR/G1/x (x = category) on the sensor nameplate, Endress+Hauser confirms compliance with the "Essential Safety Requirements" a) specified in Annex I of the Pressure Equipment Directive 2014/68/EU or b) Schedule 2 of Statutory Instruments 2016 No. 1105.
Page 135
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Page 136
For an overview of the scope of the associated Technical Documentation, refer to the following: • Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the nameplate • Endress+Hauser Operations app: Enter serial number from nameplate or scan matrix code on nameplate. Standard documentation Brief Operating instructions...
Page 137
Proline Promass E 100 EtherNet/IP Technical data Supplementary device- Safety Instructions dependent documentation Content Documentation code ATEX/IECEx Ex i XA00159D ATEX/IECEx Ex nA XA01029D cCSAus IS XA00160D INMETRO Ex i XA01219D INMETRO Ex nA XA01220D Special Documentation Content Documentation code...
Page 138
Index Proline Promass E 100 EtherNet/IP Index 0 … 9 Operating menu ......34 Design fundamentals 3-A approval .
Page 139
Proline Promass E 100 EtherNet/IP Index Error messages Installation point ......18 see Diagnostic messages Intended use .
Page 140
Index Proline Promass E 100 EtherNet/IP Static pressure ......20 Power consumption ......120 Thermal insulation .
Page 141
Proline Promass E 100 EtherNet/IP Index Shock and vibration resistance ....125 Temperature range Signal on alarm ......116 Medium temperature .