System integration
Parameter
Burst variable 0
Burst variable 1
Burst variable 2
Burst variable 3
Burst variable 4
Burst variable 5
Burst variable 6
Burst variable 7
Burst trigger mode
Burst trigger level
Min. update period
Max. update period
*
Visibility depends on order options or device settings
42
Description
For HART command 9 and 33: select the
HART device variable or the process variable.
For HART command 9 and 33: select the
HART device variable or the process variable.
For HART command 9 and 33: select the
HART device variable or the process variable.
For HART command 9 and 33: select the
HART device variable or the process variable.
For HART command 9: select the HART
device variable or the process variable.
For HART command 9: select the HART
device variable or the process variable.
For HART command 9: select the HART
device variable or the process variable.
For HART command 9: select the HART
device variable or the process variable.
Select the event that triggers burst message
X.
Enter the burst trigger value.
Together with the option selected in the
Burst trigger mode parameter the burst
trigger value determines the time of burst
message X.
Enter the minimum time span between two
burst commands of burst message X.
Enter the maximum time span between two
burst commands of burst message X.
Proline Prosonic Flow E 100 HART
Selection / User entry
• Volume flow
• Mass flow
• Flow velocity
• Temperature
• Sound velocity
*
• Signal asymmetry
*
• Acceptance rate
*
• Turbulence
*
• Signal strength
*
• Signal to noise ratio
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Percent of range
• Measured current
• Primary variable (PV)
• Secondary variable (SV)
• Tertiary variable (TV)
• Quaternary variable (QV)
• Not used
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
See the Burst variable 0
parameter.
• Continuous
• Window
• Rising
• Falling
• On change
Signed floating-point number
Positive integer
Positive integer
Factory setting
Volume flow
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Continuous
1 000 ms
2 000 ms