Proline Prosonic Flow E 100 HART
Signal on alarm
Endress+Hauser
Damping
Pulse/pause ratio
Assignable measured
variables
Switch output
Switching behavior
Switching delay
Number of switching
cycles
Assignable functions
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure mode
Pulse/frequency/switch output
Pulse output
Failure mode
Frequency output
Failure mode
Switch output
Failure mode
Adjustable: 0 to 999 s
1:1
• Volume flow
• Mass flow
• Temperature
Binary, conductive or non-conductive
Adjustable: 0 to 100 s
Unlimited
• Off
• On
• Diagnostic behavior
• Limit value
• Volume flow
• Mass flow
• Temperature
• Totalizer 1-3
• Flow direction monitoring
• Status
Low flow cut off
Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Choose from:
• Actual value
• No pulses
Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 12 500 Hz
Choose from:
• Current status
• Open
• Closed
Technical data
93