Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Setting
The table below shows the setting elements necessary for the thermal overload protection and their
setting ranges.
Element
Range
THM
0.1 – 10.0 A
(0.02 – 2.00 A)(*)
THMIP
0.0 – 5.0 A
(0.00 – 1.00 A)(*)
TTHM
0.5 - 100.0 min
THMA
50 – 99 %
[THMEN]
Off / On
[THMAEN]
Off / On
[THMRST]
Off / On
(*) Current values shown in the parenthesis are in the case of a 1 A rating. Other current
values are in the case of a 5 A rating.
Note: THMIP sets a minimum level of previous load current to be used by the thermal element,
and is only active when testing ([THMRST] = "ON").
Step
Default
0.1 A
5.0 A
(0.01 A)
(1.00 A)
0.1 A
0.0 A
(0.01 A)
(0.00 A)
0.1 min
10.0 min
1 %
80 %
Off
Off
Off
61
6 F 2 S 0 8 4 2
Remarks
Thermal overload setting.
(THM = I
: allowable overload current)
AOL
Previous load current for testing
Thermal time constant
Thermal alarm setting.
(Percentage of THM setting.)
Thermal OL enable
Thermal alarm enable
Thermal element test