Download Print this page

Toshiba GRD150 Series Instruction Manual page 103

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Element
Range
SYNDf
0.02 – 0.50 Hz
TLRDI
0.00 – 100.00 s
TDRLI
0.00 – 100.00 s
TDRDI
0.00 – 100.00 s
TSYN
0.00 – 100.00 s
[ARCEN]
Off/On
[ARCEN-S]
Off/On
[ARCEN-C]
Off/On
[ARC-NUM]
S1/S2/S3/S4/S5
[OC1-INIT]
NA/A1/A2/BLK
[OC2-INIT]
NA/A1/A2/BLK
[OC3-INIT]
NA/A1/A2/BLK
[OC4-INIT]
NA/A1/A2/BLK
[DOC1-INIT]
NA/A1/A2/BLK
[DOC2-INIT]
NA/A1/A2/BLK
[DOC3-INIT]
NA/A1/A2/BLK
[DOC4-INIT]
NA/A1/A2/BLK
[EF1-INIT]
NA/A1/A2/BLK
[EF2-INIT]
NA/A1/A2/BLK
[EF3-INIT]
NA/A1/A2/BLK
[EF4-INIT]
NA/A1/A2/BLK
[DEF1-INIT]
NA/A1/A2/BLK
[DEF2-INIT]
NA/A1/A2/BLK
[DEF3-INIT]
NA/A1/A2/BLK
[DEF4-INIT]
NA/A1/A2/BLK
[SE1-INIT]
NA/A1/A2/BLK
[SE2-INIT]
NA/A1/A2/BLK
[SE3-INIT]
NA/A1/A2/BLK
[SE4-INIT]
NA/A1/A2/BLK
[DSE1-INIT]
NA/A1/A2/BLK
[DSE2-INIT]
NA/A1/A2/BLK
[DSE3-INIT]
NA/A1/A2/BLK
[DSE4-INIT]
NA/A1/A2/BLK
[EXT-INIT]
NA/A1/A2/BLK
[APPL-VTS]
A/B/C/AB/BC/CA
[VCHK]
Non/LRDI/DRLI/DRDI/SYN
[COORD-OC]
Off/On
[COORD-EF]
Off/On
[COORD-SE]
Off/On
OC
0.2 − 250.0 A
(0.04 − 50.00 A) (*)
EF
0.2 − 250.0 A
(0.04 − 50.00 A) (*)
0.025 − 0.125 A
SEF
(0.005 − 0.025 A)
Step
Default
Remarks
0.01 Hz
0.50 Hz
Synchronism check
0.01 s
0.05 s
Voltage check time
0.01 s
0.05 s
Voltage check time
0.01 s
0.05 s
Voltage check time
0.01 s
1.00 s
Synchronism check time
On
Autoreclose enable
Off
Single-phase autoreclose enable
Off
Configurable autoreclose enable
S1
Autoreclosing shot number
A1
Autoreclose initiation by OC1
NA
Autoreclose initiation by OC2
NA
Autoreclose initiation by OC3
NA
Autoreclose initiation by OC4
NA
Autoreclose initiation by DOC1
NA
Autoreclose initiation by DOC2
NA
Autoreclose initiation by DOC3
NA
Autoreclose initiation by DOC4
NA
Autoreclose initiation by EF1
NA
Autoreclose initiation by EF2
NA
Autoreclose initiation by EF3
NA
Autoreclose initiation by EF4
NA
Autoreclose initiation by DEF1
NA
Autoreclose initiation by DEF2
NA
Autoreclose initiation by DEF3
NA
Autoreclose initiation by DEF4
NA
Autoreclose initiation by SE1
NA
Autoreclose initiation by SE2
NA
Autoreclose initiation by SE3
NA
Autoreclose initiation by SE4
NA
Autoreclose initiation by DSE1
NA
Autoreclose initiation by DSE2
NA
Autoreclose initiation by DSE3
NA
Autoreclose initiation by DSE4
NA
Autoreclose initiation by external trip command
Phase setting for Synchronism and voltage check
Non
Synchronism and voltage check
Off
OC relay for Co-ordination
Off
EF relay for Co-ordination
Off
SE relay for Co-ordination
0.1 A
5.0 A
OC for co-ordination
(0.01 A)
(1.00 A)
0.1 A
1.5 A
EF for co-ordination
(0.01 A)
(0.30 A)
0.01 A
0.050 A
SEF for co-ordination
(0.01 A)
(0.010 A)
102