Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Element
Range
[VHWAMEN]
Off / On
[VLALMEN]
Off / On
[VLWAMEN]
Off / On
[PHALMEN]
Off / On
[PHWAMEN]
Off / On
[QHALMEN]
Off / On
[QHWAMEN]
Off / On
[QLALMEN]
Off / On
[QLWAMEN]
Off / On
[fHALMEN]
Off / On
[fHWAMEN]
Off / On
[fLALMEN]
Off / On
[fLWAMEN]
Off / On
[IeHALMEN]
Off / On
[IeHWAMEN]
Off / On
[IeLALMEN]
Off / On
[IeLWAMEN]
Off / On
[VeHALMEN]
Off / On
[VeHWAMEN]
Off / On
[VeLALMEN]
Off / On
[VeLWAMEN]
Off / On
IHALM
0.0 – 999.9 kA
IHWAR
0.0 – 999.9 kA
ILALM
0.0 – 999.9 kA
ILWAR
0.0 – 999.9 kA
IHYST
0.00 – 0.10 kA
VHALM
0.0 – 999.9 kV
VHWAR
0.0 – 999.9 kV
VLALM
0.0 – 999.9 kV
VLWAR
0.0 – 999.9 kV
VHYST
0.0 – 20.0 kV
PHALM
–999.9 – 999.9 MW
PHWAR
–999.9 – 999.9 MW
PLALM
–999.9 – 999.9 MW
PLWAR
–999.9 – 999.9 MW
PHYST
0.0 – 20.0 MW
QHALM
–999.9 – 999.9 Mv
QHWAR
–999.9 – 999.9 Mv
QLALM
–999.9 – 999.9 Mv
QLWAR
–999.9 – 999.9 Mv
QHYST
0.0 – 20.0 Mv
fHALM
25.0 – 75.0 Hz
fHWAR
25.0 – 75.0 Hz
Step
Default
Remarks
Off
Voltage V high warning enable
Off
Voltage V low alarm enable
Off
Voltage V low warning enable
Off
Active power P high alarm enable
Off
Active power P high warning enable
Off
Reactive power Q high alarm enable
Off
Reactive power Q high warning enable
Off
Reactive power Q low alarm enable
Off
Reactive power Q low warning enable
Off
Frequency f high alarm enable
Off
Frequency f high warning enable
Off
Frequency f low alarm enable
Off
Frequency f low warning enable
Off
Current Ie high alarm enable
Off
Current Ie high warning enable
Off
Current Ie low alarm enable
Off
Current Ie low warning enable
Off
Voltage Ve high alarm enable
Off
Voltage Ve high warning enable
Off
Voltage Ve low alarm enable
Off
Voltage Ve low warning enable
0.1
0.0 kA
Current I high alarm
0.1
0.0 kA
Current I high warning
0.1
0.0 kA
Current I low alarm
0.1
0.0 kA
Current I low warning
0.01
0.00 kA
Current I hysteresis setting
0.1
0.0 kV
Voltage V high alarm
0.1
0.0 kV
Voltage V high warning
0.1
0.0 kV
Voltage V low alarm
0.1
0.0 kV
Voltage V low warning
0.1
0.0 kV
Voltage V hysteresis setting
0.1
0.0 MW
Active power P high alarm
0.1
0.0 MW
Active power P high warning
0.1
0.0 MW
Active power P low alarm
0.1
0.0 MW
Active power P low warning
0.1
0.0 MW
Active power P hysteresis setting
0.1
0.0 Mv
Active power P high alarm
0.1
0.0 Mv
Reactive power Q high warning
0.1
0.0 Mv
Reactive power Q low alarm
0.1
0.0 Mv
Reactive power Q low warning
0.1
0.0 Mv
Reactive power Q hysteresis setting
0.1
25.0 Hz
Frequency Q high alarm
0.1
25.0 Hz
Frequency Q high warning
116
6 F 2 S 0 8 4 2