Download Print this page

Toshiba GRD150 Series Instruction Manual page 400

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Test
Conducted RF
IEC60255-22-6,
Electromagnetic
IEC61000-4-6
Disturbance
Conducted
IEC61000-4-16 Class 3
Disturbance over freq.
Range 15Hz to
150kHz
Power Frequency
IEC60255-22-7
Disturbance
Surge Immunity
IEC60255-22-5
Conducted and
IEC60255-25
Radiated Emissions
EN55022 Class A
Power Frequency
IEC61000-4-8 Class 4
Magnetic Field
Standards
10Vrms applied over frequency range 150kHz to 100MHz.
Additional spot tests at 27 and 68MHz.
Varying voltages applied in common mode as follows:
15Hz to 150Hz: 10V → 1Vrms (20dB/decade)
150Hz to 1.5kHz: 1Vrms
1.5kHz to 15kHz: 1 → 10Vrms (20dB/decade)
15kHz to 150kHz: 10Vrms
300V 50Hz for 10s applied to ports in common mode.
100V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
1.2/50μs surge in common/differential modes:
Auxiliary power supply: 2kV/1kV (peak)
Input/Output: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions:
30 to 230MHz: <30dB
230 to 1000MHz: <37dB
Field applied at 50Hz with strengths of:
30A/m continuously,
300A/m for 1 second.
⎯ 399 ⎯