Toshiba GRD150 Series Instruction Manual page 177

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

In case of GRD150-300 or 400 series
A P P L C T
A P P L V T
A P P L V T S
<APPL VT>
To set the voltage input state (VT connection), do the following.
• If relay type is
GRD150-100 or 200 series,
key and press the ENTER key.
pressing the
or
• If relay type is
GRD150-300 or 400 series,
key and press the ENTER key.
or
<APPL VTS>
To set the voltage input state for synchronism check of autoreclose function, do the following.
• Enter "A" or "B" or "C" or "AB" or "BC" or "CA" phase by pressing the
the ENTER key.
<CTFEN, VTF1EN, VTF2EN>
To set CT failure function and VT failure function enable, do the following.
• Enter "Off" or "On" or "OPT-On" by pressing the
< CTSVEN, V0SVEN, V2SVEN>
To set AC input imbalance supervision enable, do the following.
• Enter "Off" or "ALM&BLK" or "ALM" by pressing the
key.
< CBSVEN>
To set circuit breaker supervision enable, do the following.
• Enter "Off" or "On" by pressing the
<TCSVEN>
• These settings are displayed only equipped IO card by the relay type: TCSVEN1 or 2 for IO1,
TCSVEN3 or 4 for IO2, TCSVEN5 or 6 for IO3, TCSVEN7 or 8 for IO4.
To set trip circuit supervision enable, do the following.
• Enter "Off" or "On" or "OPT-On" by pressing the
After complete settings, press the END key to display the following confirmation message.
C h a n g e s e t t i n g s ? Y = E N T E R / N = C A N C E L
• Press the ENTER (= Y) key to change settings and return to the "Protection" screen.
Setting the group
Enter the group settings as follows:
∗ ∗ ∗
∗ ∗ ∗
∗ ∗ ∗
∗ ∗ ∗
∗ ∗ ∗
∗ ∗ ∗
enter Off" or "3PN" or "3PV" or "3PP" or "2PP" by
Enter "Off" or "3PN" or "3PP" or "2PP" by pressing the
key and press the ENTER key.
or
176
or
key and press the ENTER key.
or
key and press the ENTER
or
( ∗ 2 )
key and press the ENTER key.
or
6 F 2 S 0 8 4 2