Download Print this page

Toshiba GRD150 Series Instruction Manual page 199

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

<MNC1C-IEC>
To set the NC1 Inverse Curve Type of IEC, do the following.
• Enter "NI" or "VI" or "EI" or "LTI" and press the ENTER key.
<MNC1C-IEEE>
To set the NC1 Inverse Curve Type of IEEE, do the following.
• Enter "MI" or "VI" or "EI" and press the ENTER key.
<MNC1C-US>
To set the NC1 Inverse Curve Type of US, do the following.
• Enter "CO2" or "CO8" and press the ENTER key.
< NC1R>
To set the Reset Characteristic, do the following.
• Enter "DEF" or "DEP" and press the ENTER key.
<NC∗-2F>
To set the 2f block enable of NC ∗ , do the following.
• Enter "BLK" to enable "Trip block" by the 2f element and press the ENTER key. If disabling
it, enter "NA" and press the ENTER key.
<<Element>>
• The ranges of settings are as follows:
NC1, NC2:
TNC1D, TNC2:
TNC1RD:
TNC1P, TNC1RP:
NC1-k:
NC1-a:
NC1-C:
NC1-kr:
NC1-b:
• Enter the numerical value and press the ENTER key.
• After setting, press the END key to display the following confirmation message.
C h a n g e s e t t i n g s ? Y = E N T E R / N = C A N C E L
• Press the ENTER (= Y) key to change settings and return to the "Settings menu" screen.
0.5 - 10.0 (5A rating) 0.10 - 2.00 (1A rating)
0.00 - 300.00
0.0 - 300.0
0.010 - 1.500
0.000 - 30.000
0.00 - 5.00
0.000 - 5.000
0.000 - 30.000
0.00 - 5.00
198
6 F 2 S 0 8 4 2

Advertisement