Toshiba GRD150 Series Instruction Manual page 48

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Element
Range
TDOC2D
0.00 – 300.00 s
TDOC2RD
0.0 – 300.0 s
TDOC2RP
0.010 – 1.500
(RTMS)
DOC3
0.5 – 250.0 A
(0.10 – 50.00 A)(*1)
TDOC3
0.00 – 300.00 s
DOC4
0.5 – 250.0 A
(0.10 – 50.00 A)(*1)
TDOC4
0.00 – 300.00 s
DEF1
0.05 – 25.00 A
(0.01 – 5.00 A)(*1)
TDEF1P
0.010 – 1.500
(TMS)
TDEF1D
0.00 – 300.00 s
TDEF1RD
0.0 – 300.0 s
TDEF1RP
0.010 – 1.500
(RTMS)
DEF2
0.2 – 250.0 A
(0.04 – 50.00 A)(*1)
TDEF2P
0.010 – 1.500
(TMS)
TDEF2D
0.00 – 300.00 s
TDEF2RD
0.0 – 300.0 s
TDEF2RP
0.010 – 1.500
(RTMS)
−95° – 95°
DEFθ
DEFV
0.5 – 100.0V
DEF3
0.2 – 250.0 A
(0.04 – 50.00 A)(*1)
TDEF3
0.00 – 300.00 s
DEF4
0.2 – 250.0 A
(0.04 – 50.00 A)(*1)
TDEF4
0.00 – 300.00 s
[DOC1EN]
Off / On
[MDOC1]
DT/IEC/IEEE/US/CON
[MDOC1C]
MDOC1C-IEC
NI / VI / EI / LTI
MDOC1C-IEEE
MI / VI / EI
MDOC1C-US
CO2 / CO8
Step
Default
Remarks
0.01 s
1.00 s
DOC2 definite time setting. Required if
[MDOC2] = DT.
0.1 s
0.0 s
DOC2 definite time delayed reset. Required
if [MDOC2] = IEC or [DOC2R] = DEF.
0.001
1.000
DOC2 dependent time delayed reset time
multiplier. Required if [DOC2R] = DEP.
0.1 A
50.0 A
DOC3 threshold setting
(0.01 A)
(10.00 A)
0.1 s
1.00 s
DOC3 definite time setting
0.1 A
100.0 A
DOC4 threshold setting
(0.01 A)
(20.00 A)
0.01 s
1.00 s
DOC4 definite time setting
0.01 A
1.50 A
DEF1 threshold setting
(0.01 A)
(0.30 A)
0.001
1.000
DEF1I time multiplier setting. Required if
[MDEF1] = IEC, IEEE, US or CON.
0.01 s
1.00 s
DEF1 definite time setting. Required if
[MDEF1] = DT.
0.1 s
0.0 s
DEF1I definite time delayed reset. Required
if [MDEF1] = IEC or [DEF1R] =DEF.
0.001
1.000
DEF1I dependent time delayed reset time
multiplier. Required if [DEF1R] = DEP.
0.1 A
15.0 A
DEF2 threshold setting
(0.01 A)
(3.00 A)
0.001
1.000
DEF2I time multiplier setting. Required if
[MDEF2] = IEC, IEEE, US or CON..
0.01 s
1.00 s
DEF2 definite time setting. Required if
[MDEF2] = DT.
0.1 s
0.0 s
DEF2I definite time delayed reset. Required
if [MDEF1] = IEC or [DEF2R] = DEF.
0.001
1.000
DEF2I dependent time delayed reset time
multiplier. Required if [DEF2R] = DEP.
−45°
DEF1 to DEF4 characteristic angle
0.1V
3.0V
V0 threshold setting for DEF1 to DEF4
0.01 A
25.0 A
DEF3 threshold setting
(0.01 A)
(5.00 A)
0.01 s
1.00 s
DEF3 definite time setting
0.01 A
50.0 A
DEF4 threshold setting
(0.01 A)
(10.00 A)
0.01 s
1.00 s
DEF4 definite time setting
On
DOC1 Enable
DT
DOC1 characteristic
DOC1I inverse curve type.
NI
Required if [MDOC1] = IEC.
MI
Required if [MDOC1] = IEEE.
CO2
Required if [MDOC1] = US.
47
6 F 2 S 0 8 4 2