List of Information
INF
Description
Standard Information numbers in monitor direction
System Function
0
End of General Interrogation
Transmission completion of GI items.
0
Time Synchronization
Time Synchronization ACK.
2
Reset FCB
Reset FCB(toggle bit) ACK
3
Reset CU
Reset CU ACK
4
Start/Restart
Relay start/restart
5
Pow er On
Relay pow er on.
Status Indications
If it is possible to use auto-recloser, this item is set
16 Auto-recloser active
active, if impossible, inactive.
If protection using telecommunication is available, this
17 Teleprotection active
item is set to active. If not, set to inactive.
If the protection is available, this item is set to active. If
18 Protection active
not, set to inactive.
19 LED reset
Reset of latched LEDs
Block the 103 transmission from a relay to control
20 Monitor direction blocked
system. IECBLK: "Blocked" settimg.
Transmission of testmode situation froma relay to
21 Test mode
control system. IECTST "ON" setting.
When a setting change has done at the local, the
22 Local parameter Setting
event is sent to control system.
23 Characteristic1
Setting group 1 active
24 Characteristic2
Setting group 2 active
25 Characteristic3
Setting group 3 active
26 Characteristic4
Setting group 4 active
27 Auxiliary input1
Binary input 1
28 Auxiliary input2
Binary input 2
29 Auxiliary input3
Binary input 3
30 Auxiliary input4
Binary input 4
Supervision Indications
32 Measurand supervision I
Zero sequence current supervision
33 Measurand supervision V
Zero sequence voltage supervision
35 Phase sequence supervision
Negative sequence voltage supevision
36 Trip circuit supervision
Output circuit supervision
37 I>>backup operation
38 VT fuse failure
VT failure
39 Teleprotection disturbed
CF(Communication system Fail) supervision
46 Group w arning
Only alarming
47 Group alarm
Trip blocking and alarming
Earth Fault Indications
48 Earth Fault L1
A phase earth fault
49 Earth Fault L2
B phase earth fault
50 Earth Fault L3
C phase earth fault
51 Earth Fault Fw d
Earth fault forw ard
52 Earth Fault Rev
Earth fault reverse
Contents
GI
--
--
--
--
--
GI
GI
--
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
⎯ 408 ⎯
IEC103 Configurator Default setting
Type
COT
FUN
ID
Signal No. OFF
8
10
255
6
8
255
5
3
216
5
4
216
5
5
216
Not supported
1, 7, 9, 11,
1
216
12
Not supported
1
1, 7, 9, 12
216
1
1, 7, 11, 12
216
1418
1
9, 11
216
1040
1
9, 11
216
1039
Not supported
1, 7, 9, 11,
1
216
1024
12
1, 7, 9, 11,
1
216
1025
12
1, 7, 9, 11,
1
216
1026
12
1, 7, 9, 11,
1
216
1027
12
No set
No set
No set
No set
1
1, 7, 9
216
1356
1
1, 7, 9
216
1364
1
1, 7, 9
216
1365
1
1, 7, 9
216
1359
Not supported
1
1, 7, 9
216
1342
Not supported
1
1, 7, 9
216
1346
1
1, 7, 9
216
1343
No set
No set
No set
No set
No set
6 F 2 S 0 8 4 2
DPI
ON
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
721
1
2
723
1
2
--
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2