Download Print this page

Toshiba GRD150 Series Instruction Manual page 128

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Label
Color
IN SERVICE
Green
ALARM
Red
TRIP
Red
TESTING
Red
(LED1) to (LED8)
Multi-color
(Green/Yellow/Red)
LOCAL
Red
REMOTE
Green
LED1 to LED8 are user-configurable, whose color can be selected from green, yellow and red by
MIMIC editor. Each is driven via a logic gate which can be programmed by PLC function.
The TRIP, ALARM and an operated LED if latching operation is selected, must be reset by user,
either by pressing the RESET key, by energising a binary input which has been programmed for
'Remote Reset' operation, or by a communications command. Other LEDs operate as long as a
signal is present. The RESET key is ineffective for these LEDs.
The VIEW key starts the LCD indication and switches between windows. The RESET key
clears the LCD indication and turns off the LCD backlight.
The operation keys are used to display the record, status and setting data on the LCD, input the
settings or change the settings.
The RS232C connector is a 9-way D-type connector for serial RS232C connection. This
connector is used for connection with a local personal computer.
Light emitting
diodes (LED)
To a local PC
Remarks
Lit when the relay is in service and flickered when the relay is in "Test" menu.
Lit when a failure is detected.
Lit when a trip command is issued.
Lit when test condition is set.
User-configurable
Lit when local control mode is selected.
Lit when remote control mode is selected.
IN SERVICE
ALARM
TRIP
TESTING
LOCAL
L/R
SELECT
REMOTE
Type
GRD150
Model
101A-10-10
In
1A
Vn
110V
Fn
50Hz
Vdc
110/125Vdc
Made in Japan
A
B
0V
RS232C connector
Figure 3.1.4 Front Panel
127
I
O
VIEW
ENTER
RESET
END
CANCEL
F2
F1
6 F 2 S 0 8 4 2
Liquid crystal
display
Operation keys

Advertisement

loading