Download Print this page

Toshiba GRD150 Series Instruction Manual page 25

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Element
Range
TOC2RP
0.010 – 1.500
(RTMS)
OC3
0.5 – 250.0 A
(0.10 – 50.00 A)(*1)
TOC3
0.00 – 300.0 s
OC4
0.5 – 250.0 A
(0.10 – 50.00 A)(*1)
TOC4
0.0 – 300.0 s
EF1
0.05 – 25.00 A
(0.01 – 5.00 A)(*1)
TEF1P
0.010 – 1.500
(TMS)
TEF1D
0.00 – 300.00 s
TEF1RD
0.0 – 300.0 s
TEF1RP
0.010 – 1.500
(RTMS)
EF2
0.2 – 250.0 A
(0.04 – 50.00 A)(*1)
TEF2P
0.010 – 1.500
(TMS)
TEF2D
0.00 – 300.00 s
TEF2RD
0.0 – 300.0 s
TEF2RP
0.010 – 1.500
(RTMS)
EF3
0.2 – 250.0 A
(0.04 – 50.00 A)(*1)
TEF3
0.00 – 300.00 s
EF4
0.2 – 250.0 A
(0.04 – 50.00 A)(*1)
TEF4
0.00 – 300.00 s
[OC1EN]
Off / On
[MOC1]
DT/IEC/IEEE/US/CON
[MOC1C]
MOC1C-IEC
NI / VI / EI / LTI
MOC1C-IEEE
MI / VI / EI
MOC1C-US
CO2 / CO8
[OC1R]
DEF / DEP (*2)
[OC1-2F]
NA / BLK
[OC2EN]
Off / On
[MOC2]
DT/IEC/IEEE/US/CON
[MOC2C]
MOC2C-IEC
NI / VI / EI / LTI
Step
Default
Remarks
0.001
1.000
OC2-I dependent time delayed reset time
multiplier. Required if [OC2R] = DEP.
0.1 A
50.0 A
OC3D threshold setting
(0.01 A)
(10.00 A)
0.01 s
1.00 s
OC3D definite time setting
0.1 A
100.0 A
OC4D threshold setting
(0.01 A)
(20.00 A)
0.01 s
1.00 s
OC4D definite time setting
0.01 A
1.50 A
EF1 threshold setting
(0.01 A)
(0.30 A)
0.001
1.000
EF1I time multiplier setting. Required if
[MEF1] = IEC, IEEE, US or CON.
0.01 s
1.00 s
EF1D definite time setting. Required if
[MEF1] = DT.
0.1 s
0.0 s
EF1I definite time delayed reset. Required if
[MEF1] = IEC or [EF1R] = DEF.
0.001
1.000
EF1I dependent time delayed reset time
multiplier. Required if [EF1R] = DEP.
0.1 A
15.0 A
EF2 threshold setting
(0.01 A)
(3.00 A)
0.001
1.000
EF2I time multiplier setting. Required if
[MEF2] = IEC, IEEE, US or CON.
0.01 s
1.00 s
EF2D definite time setting. Required if
[MEF2] = DT.
0.1 s
0.0 s
EF2I definite time delayed reset. Required if
[MEF2] = IEC or [EF2R] = DEF.
0.001
1.000
EF2I dependent time delayed reset time
multiplier. Required if [EF2R] = DEP.
25.0 A
EF3D threshold setting
0.1 A
(0.01 A)
(5.00 A)
0.01 s
1.00 s
EF3D definite time setting
0.1 A
50.0 A
EF4D threshold setting
(0.01 A)
(10.00 A)
0.01 s
1.00 s
EF4D definite time setting
Off
OC1 Enable
DT
OC1 characteristic
OC1I inverse curve type.
NI
Required if [MOC1] = IEC.
MI
Required if [MOC1] = IEEE.
CO2
Required if [MOC1] = US.
DEF
OC1I reset characteristic. Required if
[MOC1] = IEEE, US or CON.
NA
Blocked by ICD
Off
OC2 Enable
DT
OC2 characteristic
OC2I inverse curve type.
NI
Required if [MOC2] = IEC.
24
6 F 2 S 0 8 4 2

Advertisement

loading