Setting the Disturbance Record
To change the Disturbance Record setting, do the following:
• Select "Disturbance Record" on the "Record" screen to display the "Disturbance Record"
screen.
S e t t i n g s - R e c o r d
D i s t u r b a n c e R e c o r d
A I s a m p l i n g
O p e r a t i o n m o d e
R e c o r d t i m e
P r e - t r i g P O S
O P T 1
O P T 2
O P T 3
O P T 4
O P T 5
O P T 6
O P T 7
O P T 8
( ∗ 1 ) : "SEF" is only displayed if the model is GRD150-200 or 400 series.
<<Scheme switch>>
<AI sampling>
To set the, do the following.
• Enter "24" or "48" and press the ENTER key.
<Operation mode Mode>
To set the, do the following.
• Enter "OW" (Overwrite) or "SAT" (Saturation) and press the ENTER key.
<OPT∗ >
• Enter "On" to use as a starter. If not to be used as a starter, enter "Off".
Note: Starter elements OPT1- OPT8 are set by PLC function.
<<Element>>
• The ranges of settings are as follows:
Record time:
Pre-trig POS:
OC:
EF:
SEF:
NOC:
OV:
UV, ZOV, NOV:
• Enter the numerical value and press the ENTER key.
∗ ∗ ∗
∗ ∗ ∗
# # . # s
# # # %
∗ ∗ ∗
∗ ∗ ∗
O C
∗ ∗ ∗
∗ ∗ ∗
E F
∗ ∗ ∗
∗ ∗ ∗
S E F
∗ ∗ ∗
∗ ∗ ∗
N O C
∗ ∗ ∗
∗ ∗ ∗
O V
∗ ∗ ∗
∗ ∗ ∗
U V
∗ ∗ ∗
∗ ∗ ∗
Z O V
∗ ∗ ∗
∗ ∗ ∗
N O V
0.1 - 60.0
0 - 100
0.5 – 250.0 (5A rating)
0.5 – 125.0 (5A rating)
0.025 – 0.125 (5A rating) 0.005 - 0.025 (1A rating)
0.5 – 10.0 (5A rating)
10.0 - 200.0
1.0 - 130.0
217
2 5 / F e b / 2 0 0 3 0 9 : 4 5
∗ ∗ ∗
∗ ∗ ∗
# # . # s
# # # %
# # # . # A
# # # . # A
# # # . # A
# # # . # A
# . # # A
# . # # A
# # . # A
# # . # A
# # # . # V
# # # . # V
# # # . # V
# # # . # V
# # # . # V
# # # . # V
# # # . # V
# # # . # V
0.10 - 50.00 (1A rating)
0.10 - 25.00 (1A rating)
0.10 - 2.00 (1A rating)
6 F 2 S 0 8 4 2
( ∗ 1 )