• Enter "ENA" (Enable) for the assigned BO and press the ENTER key to operate the output
relay forcibly.
• After completing the entries, press the END key to display the following confirmation
message on the bottom line.
O p e r a t e ? Y = P r e s s i n g E N T E R
• Keep pressing the ENTER (= Y) key to operate the assigned output relays. Check that the BO
operates.
• Release pressing the ENTER key to reset the operation.
• Press the CANCEL key to return to the upper "Test" screen.
Control circuit
The control function is checked by MIMIC operation.
• Enter "Test" on the "Test-switch" screen not to disturb other GRD150s or bay control units.
• Open the "MIMIC" view screen and set the local control mode by L/R key. Select a device
(e.g. CB, DS, etc.) and open (press
device is open or close, or the assigned BO operates. See Section 4.1.1 and 4.2.3.
N = C A N C E L
key) or close (pres
272
6 F 2 S 0 8 4 2
key) the device. Check the