Download Print this page

Toshiba GRD150 Series Instruction Manual page 182

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

<MOC∗C-IEEE>
To set the OC ∗ Inverse Curve Type of IEEE, do the following.
• Enter "MI" or "VI" or "EI" and press the ENTER key.
<MOC∗C-US>
To set the OC ∗ Inverse Curve Type of US, do the following.
• Enter "CO2" or "CO8" and press the ENTER key.
< OC∗R >
To set the reset characteristic [OC ∗ R], do the following.
• Enter "DEF" or "DEP" and press the ENTER key.
<OC∗-2F>
To set the 2f block enable of OC ∗ , do the following.
• Enter "BLK" to enable "Trip block" by the 2f element and press the ENTER key. If disabling
it, enter "NA" and press the ENTER key.
<OC∗-TP∗>
To set the trip mode of OC ∗ , do the following.
• Enter "Off" (OC ∗ disable ) or "INST" (Instantaneous action) or "SET" (Action by time delay
settings) and press the ENTER key.
<<Element>>
• The ranges of settings are as follows:
OC1:
TOC1D, TOC2D:
TOC1RD, TOC2RD:
TOC1P, TOC1RP, TOC2P, TOC2RP:
OC2, OC3, OC4:
TOC3, TOC4:
OC1-k, OC2-k:
OC1-a, OC2-a:
OC1-C, OC2-C:
OC1-kr, OC2-kr:
OC1-b, OC2-b:
• Enter the numerical value by pressing the
• After setting, press the END key to display the following confirmation message.
C h a n g e s e t t i n g s ? Y = E N T E R / N = C A N C E L
• Press the ENTER (= Y) key to change settings and return to the "Settings menu" screen.
0.2 - 25.0 (5A rating) 0.04 - 5.00 (1A rating)
0.00 - 300.00
0.0 - 300.0
0.5 - 250.0 (5A rating)
0.00 - 300.00
0.000 - 30.000
0.00 - 5.00
0.000 - 5.000
0.000 - 30.000
0.00 - 5.00
key and press the ENTER key.
or
181
6 F 2 S 0 8 4 2
0.010 - 1.500
0.10 - 50.00 (1A rating)

Advertisement