Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

<MSE∗C-IEEE>
To set the SE ∗ Inverse Curve Type of IEEE, do the following.
• Enter "MI" or "VI" or "EI" and press the ENTER key.
<MSE∗C-US>
To set the SE ∗ Inverse Curve Type of US, do the following.
• Enter "CO2" or "CO8" and press the ENTER key.
<SE∗R>
To set the Reset Characteristic [SE ∗ R], do the following.
• Enter "DEF" or "DEP" and press the ENTER key.
<SE1S2>
To set the SEF1 stage 2 timer enable, do the following.
• Enter "On" to enable the SEF1 stage 2 timer and press the ENTER key. If disabling it, enter
"Off" and press the ENTER key.
<SE∗-2F>
To set the 2f block enable of SE ∗ , do the following.
• Enter "BLK" to enable "Trip block" by the 2f element and press the ENTER key. If disabling
it, enter "NA" and press the ENTER key.
<SE∗-TP∗>
To set the trip mode of SE ∗ , do the following.
• Enter "Off" (SE ∗ disable ) or "INST" (Instantaneous action) or "SET" (Action by time delay
setting) and press the ENTER key.
<<Element>>
• The ranges of settings are as follows:
SE1, SE2, SE3, SE4:
TSE1D, TSE1S2, TSE2D: 0.00 - 300.00
TSE1RD, TSE2RD:
TSE1P, TSE1RP, TSE2P, TSE2RP:
TSE3, TSE4:
SE1-k, SE2-k:
SE1-a, SE2-a:
SE1-C, SE2-C:
SE1-kr, SE2-kr:
SE1-b, SE2-b:
• Enter the numerical value and press the ENTER key.
• After setting, press the END key to display the following confirmation message.
0.025 - 0.125A (5A rating)
0.0 - 300.0
0.00 - 300.00
0.000 - 30.000
0.00 - 5.00
0.000 - 5.000
0.000 - 30.000
0.00 - 5.00
193
6 F 2 S 0 8 4 2
0.005 - 0.025A (1A rating)
0.010 - 1.500