Toshiba GRD150 Series Instruction Manual page 241

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

• Enter "ENA" (Enable) and press the ENTER key to operate the output relays forcibly.
• After completing the entries, press the END key to display the following confirmation
message on the bottom line.
O p e r a t e ? Y = P r e s s i n g E N T E R
• Keep pressing the ENTER (= Y) key to operate the assigned output relays.
• Release pressing the ENTER key to reset the operation.
• Press the CANCEL key to return to the upper "Test" screen.
4.2.7.3 Logic circuit
It is possible to observe the binary signal level on the signals listed in Appendix C with monitoring
jacks A and B.
To display logic circuit, do the following:
• Select "Logic circuit" to display the "Logic circuit" screen.
T e s t - L o g i c c i r c u i t
T e r m A
T e r m B
• Enter a signal number (0 - 3071) to be observed at monitoring jack A and press the ENTER
key.
• Enter the other signal number (0 - 3071) to be observed at monitoring jack B and press the
ENTER key.
After completing the setting, the signals can be observed by the binary logic level at monitoring
jacks A and B or by the LEDs above the jacks.
On screens other than the above screen, observation with the monitoring jacks is disabled.
N = C A N C E L