Toshiba GRD150 Series Instruction Manual page 109

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

and select enable signal which made in internal logic.
CB_CL_CNTL is given by CB_SELECTED and close command from PLC/panel/remote system
and close enable signal which made in internal logic. In addition, CB_CL_OUT is given for
device control. It is kept till the timer "CBCLP" count up in case of [CBPM] "Var", or till changed
device status. CB_CL_OUT must be assign to BO by PLC function.
+
CB on MIMIC diagram
2338
CB_SELCMD
Local
&
Select on panel
Remote
&
Select from
Communication
Select enable
2340
CB_CLCMD
Local
&
|(bar) on panel
Remote
&
Close from
Communication
Close enable
2304
CB_N/O_CONT
(Note) CB_SELCMD: CB select command assigned by PLC.
CB_CLCMD:
CB close command assigned by PLC.
CB_N/O CONT: CB N/O contact assigned by PLC
Figure 2.6.4
CB pulse mode [CBPM] is as follows:
The pulse mode can be set to "Fix" or "Var". When "Fix" selected, the control output turns OFF
automatically after the device responds. If the device does not respond, the control output turns off
after the setting time of CB response check timer CBRSPT has passed. When "Var" selected, the
control output is ON during the setting time of CBCLP or CBOPP. (For the setting range, see
2.6.2.7.)
When CBPM = Fix selected,
1) If the device responds,
Control output
OPEN
52a (N/O)
52b (N/C)
2) If the device does not respond,
Control output
OPEN
52a (N/O)
52b (N/C)
≥1
&
&
+
≥1
Scheme Logic of CB Close and Control Operation
ON
OFF
108
CBCLP
[CBPM]
&
"Var"
0.1 - 100.0s
&
F/F
"Fix"
6 F 2 S 0 8 4 2
912
CB_ENABLE
768
CB_SELECTED
821
CB_CL_CNTL
865
CB_CL_OUT
≥1