Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

and b. The following table shows the setting ranges of the curve defining constants.
Curve defining constants
k
a
c
kr
b
IEC/UK Inverse Curves
(Time Multiplier = 1)
1000
100
10
1
0.1
1
10
Current (Multiple of Setting)
Programmable Reset Characteristics
OC1-I, OC2-I, EF1-I, EF2-I, SEF1-I, SEF2-I and NOC1-I have a programmable reset feature:
instantaneous, definite time delayed, or dependent time delayed reset. (Refer to Appendix A for a
more detailed description.)
Instantaneous resetting is normally applied in multi-shot auto-reclosing schemes, to ensure correct
grading between relays at various points in the scheme.
The inverse reset characteristic is particularly useful for providing correct coordination with an
upstream induction disc type overcurrent relay.
The definite time delayed reset characteristic may be used to provide faster clearance of
intermittent ('pecking' or 'flashing') fault conditions.
Range
Step
0.000 – 30.000
0.001
0.00 – 5.00
0.01
0.000 – 5.000
0.001
0.000 – 30.000
0.001
0.00 – 5.00
0.01
100
10
LTI
NI
1
VI
EI
0.1
100
Figure 2.1.3
IDMT Characteristics
14
Remarks
Operating characteristic
([M∗∗∗]=CON setting)
Resetting characteristic
([M∗∗∗]=CON, and [∗∗∗R]=DEP setting)
IEEE/US Inverse Curves
(Time Multiplier = 1)
1
10
Current (Multiple of Setting)