Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

Element
Range
TDSE1S2
0.00 – 300.00 s
DSE2
0.025 – 0.125 A
(0.005 – 0.025 A)(*1)
TDSE2P
0.010 – 1.500
(TMS)
TDSE2D
0.00 – 300.00 s
TDSE2RD
0.0 – 300.0 s
TDSE2RP
0.010 – 1.500
(RTMS)
DSE3
0.025 – 0.125 A
(0.005 – 0.025 A)(*1)
TDSE3
0.00 – 300.00 s
DSE4
0.025 – 0.125 A
(0.005 – 0.025 A)(*1)
TDSE4
0.00 – 300.00 s
[DSE1EN]
Off / On
[MDSE1]
DT/IEC/IEEE/US/CON
[MDSE1C]
MDSE1C-IEC
NI / VI / EI / LTI
MDSE1C-IEEE
MI / VI / EI
MDSE1C-US
CO2 / CO8
[DSE1R]
DEF / DEP (*2)
[DSE1S2]
Off / On
[DSE1-DIR]
FWD / REV
[DSE1-2F]
NA / BLK
[DSE2EN]
Off / On
[MDSE2]
DT/IEC/IEEE/US/CON
[MDSE2C]
MDSE2C-IEC
NI / VI / EI / LTI
MDSE2C-IEEE
MI / VI / EI
MDSE2C-US
CO2 / CO8
[DSE2R]
DEF / DEP (*2)
[DSE2-DIR]
FWD / REV
[DSE2-2F]
NA / BLK
[DSE3EN]
Off / On
[DSE3-2F]
NA / BLK
[DSE4EN]
Off / On
[DSE4-2F]
NA / BLK
RPEN
Off / On
(*1) Current values shown in parenthesis are in the case of a 1 A rating. Other current values are in
the case of a 5 A rating.
(*2) DEF: Instant or Definite time, DEP: Inverse time
Step
Default
Remarks
0.01 s
1.00 s
DSEF1 stage 2 definite time setting
0.001 A
0.050 A
DSEF2 threshold setting
(0.001 A)
(0.010 A)
0.001
1.000
DSEF2I inverse time multiplier setting.
Required if [MDSE2] = IEC, IEEE, US or CON.
0.01 s
1.00 s
DSEF2 definite time setting. Required if
[MDSE2] = DT.
0.1 s
0.0 s
DSEF2I definite time delayed reset. Required
if [MDSE1] = IEC or [DSE2R] = DEF.
0.001
1.000
DSEF2I dependent time delayed reset time
multiplier. Required if [DSE2R] = DEP.
0.001 A
0.050 A
DSEF3 threshold setting
(0.001 A)
(0.010 A)
0.01 s
1.00 s
DSEF3 definite time setting.
0.001 A
0.050 A
DSEF4 threshold setting
(0.001 A)
(0.010 A)
0.01 s
1.00 s
DSEF4 definite time setting.
On
DSEF1 Enable
DT
DSEF1 characteristic
DSE1-I inverse curve type.
NI
Required if [MDSE1] = IEC.
MI
Required if [MDSE1] = IEEE.
CO2
Required if [MDSE1] = US.
DEF
DSEF1-I reset characteristic. Required if
[MDSE1] = IEEE, US or CON.
Off
DSEF1 stage 2 timer enable
FWD
DSEF1 directional characteristic
NA
Blocked by ICD
Off
DSEF2 Enable
DT
DSEF2 characteristic
DSE2-I inverse curve type.
NI
Required if [MDSE2] = IEC.
MI
Required if [MDSE2] = IEEE.
CO2
Required if [MDSE2] = US.
DEF
DSEF2-I reset characteristic. Required if
[MDSE2] = IEEE, US or CON.
FWD
DSEF2 directional characteristic
NA
Blocked by ICD
Off
DSEF3 Enable
NA
Blocked by ICD
Off
DSEF4 Enable
NA
Blocked by ICD
Off
Residual power block enable
52
6 F 2 S 0 8 4 2