Toshiba GRD150 Series Instruction Manual page 101

Feeder manager
Hide thumbs Also See for GRD150 Series:

Advertisement

ARC IN-PROG
&
ARC1 INIT
SP2
ARC-SHOT2
(Trip command)
&
SP3
&
SP4
ARC-SHOT4
&
SP5
&
ARC2 INIT
(Trip command)
SP2
ARC-SHOT2
&
SP3
ARC-SHOT3
&
SP4
ARC-SHOT4
&
SP5
Figure 2.5.3 Scheme Logic of Second to Fifth Shot Autoreclose
Sequence coordination
Co-ordination is maintained between the autoreclose sequences of adjacent relays on a feeder.
This means that a relay will register the flow of fault current and increment through its autoreclose
sequence even if another relay actually carries out the tripping and reclosing operations. This
function is initiated by the operation of OC, EF or SEF element, and can be disabled by the scheme
switch [COORD-OC], [COORD-EF] or [COORD-SE].
The reclose shot number at the local terminal A is coordinated with that at the adjacent terminal B
as shown in Figure 2.5.4.
T1S2
t
0
S
F/F
0.01-300.00s
R
T1S2R
t
0
0.01-310.00s
T1S3
t
0
S
F/F
0.01-300.00s
R
T1S3R
ARC-SHOT3
t
0
0.01-310.00s
T1S4
t
0
S
F/F
0.01-300.00s
R
T1S4R
t
0
0.01-310.00s
T1S5
t
0
S
F/F
0.01-300.00s
R
T1S5R
ARC-SHOT5
t
0
0.01-310.00s
T2S2
t
0
S
F/F
0.01-300.00s
R
T2S2R
t
0
0.01-310.00s
T2S3
t
0
S
F/F
0.01-300.00s
R
T2S3R
t
0
0.01-310.00s
T2S4
t
0
S
F/F
0.01-300.00s
R
T2S4R
t
0
0.01-310.00s
T2S5
t
0
S
F/F
0.01-300.00s
R
T2S5R
ARC-SHOT5
t
0
0.01-310.00s
A
GRD150
Figure 2.5.4
100
547
&
1652
ARC1-S2 COND
ARC1-S2 TRR
548
&
1653
ARC1-S3 COND
ARC1-S3 TRR
549
&
1654
ARC1-S4 COND
ARC1-S4 TRR
550
&
1655
ARC1-S5 COND
ARC1-S5 TRR
555
&
1668
ARC2-S2 COND
ARC2-S2 TRR
556
&
1669
ARC2-S3 COND
ARC2-S3 TRR
557
&
1670
ARC2-S4 COND
ARC2-S4 TRR
558
&
1671
ARC2-S5 COND
ARC2-S5 TRR
B
GRD150
Sequence Coordination
6 F 2 S 0 8 4 2
539
ARC-SHOT2
≥1
540
ARC-SHOT3
≥1
541
ARC-SHOT4
≥1
542
ARC-SHOT5
≥1
Fault