Mechanical design
Weight
Case color
Installation
Connection terminals
TB1:
TB2 – TB10:
ENVIRONMENTAL PERFORMANCE
Test
Atmospheric Environment
Temperature
Humidity
Enclosure Protection
Mechanical Environment
Vibration
Shock and Bump
Seismic
High Voltage Environment
Dielectric Withstand
High Voltage Impulse
Electromagnetic Environment
High Frequency
Disturbance /
Damped Oscillatory
Wave
Electrostatic
Discharge
Radiated RF
Electromagnetic
Disturbance
Fast Transient
Disturbance
8.9 kg (Standard model)
2.5Y7.5/1(approximation to Munsell value)
Flush mounting
M3.5 Ring terminal
Phoenix Contact, UK MSTB
Direct cable connection: AWG24 to AWG12 recommended,
Cable ferrule: AI 2,5-10BU from Phoenix Contact is
Standards
IEC60068-2-1/2
IEC60068-2-3
IEC60529
IEC60255-21-1
IEC60255-21-2
IEC60255-21-3
IEC60255-5
IEC60255-5
IEC60255-22-1 Class 3,
IEC61000-4-12
IEC60255-22-2 Class 3,
IEC61000-4-2
(
)
IEC60255-22-3 Class 3
*
,
IEC61000-4-3
Note (∗): Class 4 with cover
IEC60255-22-4,
IEC61000-4-4
⎯ 398 ⎯
recommended for AWG14 (cross-section 2mm
AI 1,5-10BK from Phoenix Contact is
recommended for AWG16 (cross-section 1.25mm
Details
Operating range: −10°C to +55°C.
Storage / Transit: −25°C to +70°C.
56 days at 40°C and 93% relative humidity.
Front: IP51 or IP52 with cover
Rear: IP20
Response - Class 1
Endurance - Class 1
Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Class 1
2kVrms for 1 minute between all terminals and earth.
2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
Three positive and three negative impulses of 5kV(peak),
1.2/50μs, 0.5J between all terminals and between all
terminals and earth.
1MHz 2.5kV applied to all ports in common mode.
1MHz 1.0kV applied to all ports in differential mode.
6kV contact discharge.
8kV air discharge.
Field strength 10V/m for frequency sweeps of 80MHz to
1GHz and 1.7GHz to 2.2GHz. Additional spot tests at 80,
160, 450, 900 and 1890MHz.
4kV, 2.5kHz, 5/50ns applied to all inputs.
6 F 2 S 0 8 4 2
stripping length is 10mm.
2
).
2
).