and output relays. Operation of the output contacts is monitored at the output terminal. The output
contact and corresponding terminal number are shown in Appendix G.
T e s t M e n u
S w i t c h
B i n a r y O / P
L o g i c c i r c u i t
Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. The LCD
displays the output modules installed depending on the model.
T e s t - B i n a r y O / P
I O 1
T R P 1 : T B 3 - 1 9 , 2 0
T R P 2 : T B 4 - 1 ,
B O 1 : T B 4 - 5 ,
B O 2 : T B 4 - 7 ,
B O 3 : T B 4 - 9 , 1 0
B O 4 : T B 4 - 1 1 , 1 2
B O 5 : T B 4 - 1 3 , 1 4
2 8 F
: T B 4 - 1 5 , 1 7
• Enter the selected number corresponding to each module to be operated. The LCD will display
the name of the module, the name of the output relay, the name of the terminal block and the
terminal number to which the relay contact is connected.
• Enter "ENA" (Enable) and press the ENTER key to operate the output relays forcibly.
• After completing the entries, press the END key to display the following confirmation
message on the bottom line.
O p e r a t e ? Y = P r e s s i n g E N T E R
• Keep pressing the ENTER (= Y) key to operate the assigned output relays.
• Release pressing the ENTER key to reset the operation.
• Check that the output contacts operate at the terminal.
2 5 / F e b / 2 0 0 3 0 9 : 4 5
2 5 / F e b / 2 0 0 3 0 9 : 4 5
I O 2
∗ ∗ ∗
T R P 1 : T B 5 - 1 9 , 2 0
∗ ∗ ∗
2
T R P 2 : T B 6 - 1 ,
∗ ∗ ∗
6
B O 1 : T B 6 - 5 ,
∗ ∗ ∗
8
B O 2 : T B 6 - 7 ,
∗ ∗ ∗
B O 3 : T B 6 - 9 , 1 0
∗ ∗ ∗
B O 4 : T B 6 - 1 1 , 1 2
∗ ∗ ∗
B O 5 : T B 6 - 1 3 , 1 4
∗ ∗ ∗
B O 6 : T B 6 - 1 5 , 1 7
N = C A N C E L