To set the DEF ∗ Inverse Curve Type of IEC, do the following.
• Enter "NI" or "VI" or "EI" or "LTI" and press the ENTER key.
<MDSE∗C-IEEE>
To set the DEF ∗ Inverse Curve Type of IEEE, do the following.
• Enter "MI" or "VI" or "EI" and press the ENTER key.
<MDSE∗C-US>
To set the DEF ∗ Inverse Curve Type of US, do the following.
• Enter "CO2" or "CO8" and press the ENTER key.
<DSE∗R>
To set the Reset Characteristic, do the following.
• Enter "DEF" or "DEP" and press the ENTER key.
<DSE1S2>
To set the DSEF1 stage 2 timer enable, do the following.
• Enter "On" to enable the DSEF1 stage 2 timer and press the ENTER key. If disabling it, enter
"Off" and press the ENTER key.
<DSE∗-2F>
To set the 2f block enable of DSE ∗ , do the following.
• Enter "BLK" to enable "Trip block" by the 2f element and press the ENTER key. If disabling
it, enter "NA" and press the ENTER key.
<DSE∗-TP∗>
To set the trip mode of DSE ∗ , do the following.
• Enter "Off" (DSE ∗ disable ) or "INST" (Instantaneous action) or "SET" (Action by time delay
setting) and press the ENTER key.
<RPEN>
To set the residual power to enable, do the following.
• Enter "On" to enable the residual power and press the ENTER key. If disabling it, enter "Off"
and press the ENTER key.
<<Element>>
• The ranges of settings are as follows:
DSE θ :
DSEV:
DSE1 DSE2, DSE3, DSE4: 0.025 - 0.125A (5A rating) 0.005 - 0.025A (1A rating)
− 95 - 95
0.5 - 100.0