3 SPECIFICATIONS
Device
Signal Name
No.
X12
Logging error
CPU event
X13
monitor error
Tag event monitor
X14
error
Time event
X15
monitor error
Access target
X16
CPU error
E-mail
X17
transmission error
X18
FTP transfer error
X19
Connection error
X1C
Other error
Watch dog timer
X1F
error
3 - 17
(1) Turns on when a logging error occurs.
(2) When this turns on, an error code is stored into the logging status area (buffer memory:
2000 to 2267).
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when an error of CPU event monitor occurs.
(2) When this turns on, an error code is stored into the CPU event monitor status area 1
(buffer memory: 3300 to 3375). ( )
The statuses of CPU monitor setting No. 1 to 16 are also stored into the CPU event
monitor status area 2 (buffer memory: 3000 to 3018).
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when an error of tag event monitor occurs.
(2) When this turns on, an error code is stored into the tag event monitor status area 1
(buffer memory: 10000 to 10447). ( )
The statuses of tag monitor setting No. 1 to 16 are also stored into the tag event
monitor status area 2 (buffer memory: 3100 to 3118).
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when an error of time event monitor occurs.
(2) When this turns on, an error code is stored into the time/interval monitor status area
(buffer memory: 3200 to 3217).
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when a communication error of the access target CPU occurs.
(2) When this turns on, an error code is stored into the access target CPU setting status
area (buffer memory: 4000 to 4071).
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when an e-mail transmission error occurs.
(2) When this turns on, an error code is stored into the e-mail transmission status area
(buffer memory: 5000 to 5984).
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when an FTP transfer error occurs.
(2) When this turns on, an error code is stored into the following area of the buffer memory.
(a) Error related to FTP transfer (PUT): FTP client status (PUT) area (buffer memory:
6002 to 6553)
(b) Error related to FTP transfer (GET): FTP client status (GET) area (buffer memory:
8002 to 8553)
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when network connection fails.
(2) When this turns on, an error code is stored into the connection error code area (buffer
memory: 30).
(3) Turns off when Error clear request (Y10) is turned on.
(1) Turns on when an error not corresponding to X11 to X19 occurs.
(2) When this turns on, the error code is stored into the error log area (buffer memory: 150
to 247).
(3) Turns off when Error clear request (Y10) is turned on. (Only when the module continue
error occurs)
Turns on when a watch dog timer error occurs.
Description
MELSEC-Q
3 - 17