9 TROUBLE SHOOTING
Error
Error name
code
Tag event monitor
063Fh
component non-setting
error
Tag event monitor
0640h
component type error
Tag event condition
0641h
setting error
Tag event monitor
0642h
attached file error
Time/Interval event
0643h
monitor time setting
error
Time/Interval event
0644h
monitor attached file
error
CPU event e-mail
0645h
setting error
Tag event e-mail
0646h
setting error
Time/Interval event e-
0647h
mail setting error
0648h
Setting mismatch error
Duplicate high speed
0649h
tag specification error
9 - 31
Error definition
The component specified in
"Component name" of the tag
event setting does not exist.
The data type of the component
specified in "Component name" of
the tag event setting is a string
type.
Invalid setting was made in
"Condition" of the tag event
setting, or the event setting file is
destroyed.
Invalid setting was made in
"Attached file" of the tag event
setting.
Invalid setting was made in
"Time/Interval" of the time/interval
event setting.
Invalid setting was made in
"Attached file" of the time/interval
event setting.
Though the e-mail setting was
made in the CPU event setting,
the destination was not specified
in the common setting.
Though the e-mail setting was
made in the tag event setting, the
destination was not specified in
the common setting.
Though the e-mail setting was
made in the time/interval event
setting, the destination was not
specified in the common setting.
Setting update was performed
after the monitor screen was
displayed.
The tag setting file is corrupted.
(From the previous page)
Corrective action
• Check the tag event setting.
(Refer to Section 6.5.3)
• Check the tag event setting.
(Refer to Section 6.5.3)
• After initializing the module (refer
to Section 4.13), perform the
event setting (refer to Section
6.5.3) again.
• Check the tag event setting.
(Refer to Section 6.5.3)
• Check the time/interval event
setting. (Refer to Section 6.5.3)
• Check the time/interval event
setting. (Refer to Section 6.5.3)
• Check the CPU event setting.
(Refer to Section 6.5.3)
• Check the tag event setting.
(Refer to Section 6.5.3)
• Check the time/interval event
setting.
(Refer to Section 6.5.3)
• Display the monitor screen again
after selecting the monitor screen
to be executed from the monitor
screen menu again.
• Initialize the module (refer to
Section 4.13) and then make the
tag setting (refer to Section 6.3.3)
again.
(Continued on the next page)