Mitsubishi MELSEC-Q Series User Manual page 258

Web server module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

6 FUNCTIONS
6 - 56
(a)
CPU name
1)
Set the CPU name to be monitored.
2)
Select the CPU name set in the access target CPU setting.
(Refer to Section 4.6.7 for the access target CPU setting.)
3)
The CPU name drop-down list displays the setting No. and CPU
names of the access target CPU setting.
(Example) 01: Control CPU
4)
By default, the host CPU of the Web server module is set as the
access target CPU setting No. 1.
(b)
Interval
1)
Set the CPU event monitor interval. (1 to 86400 seconds)
2)
A CPU event occurs once when the Web server module starts or the
setting is updated, and thereafter at the specified interval.
(c)
Condition
1)
Set conditions for monitoring of the CPU event.
More than one conditions can be specified for one programmable
controller CPU.
When more than one conditions have been specified, an event occurs
if any of them is satisfied.
Item
Normal STOP
Normal RUN
PAUSE
Warning STOP( 1)
Warning RUN
System Error
1 In the QCPU (Q mode) function version A, QCPU (A mode), QnACPU and
ACPU, a warning STOP does not occur when the programmable
controller CPU is stopped with a continue error. (A system error occurs.)
2)
When the programmable controller CPU returns to the status other
than the specified condition, the event is restored.
When more than one condition have been specified, the event is
restored when the programmable controller CPU returns to the status
other than all the conditions.
(d)
Send an e-mail when an event occurs.
1)
Set whether e-mail will be sent upon event occurrence or not.
2)
Refer to Section 6.6.6 for e-mail transmission by the event monitor
function.
The programmable controller CPU is stopped with no error.
The programmable controller CPU is running with no error.
The programmable controller CPU is pausing.
The programmable controller CPU is stopped with a continue error.
The programmable controller CPU is running with a continue error.
The programmable controller CPU is in a stop error status or cannot
communicate with the target programmable controller CPU (e.g.
network error).
MELSEC-Q
Description
6 - 56

Advertisement

Table of Contents
loading

Table of Contents