2 SYSTEM CONFIGURATION
2
Programmable
controller CPU
C Controller module
2 - 2
Applicable CPU module
CPU type
CPU model
Q03UDECPU
Q04UDEHCPU
Universal model
Q06UDEHCPU
QCPU (*5) (*6) (*7)
Q13UDEHCPU
Q26UDEHCPU
Safety CPU
QS001CPU
Q06CCPU-V
Q06CCPU-V-B
1 Limited within the range of I/O points for the CPU module.
2 Can be installed to any I/O slot of a base unit.
3 Use the Web server module whose serial No.(first five digits) is 09012 or
later.
4 The redundant CPU can access its own station only.
Access to another station is not allowed.
5 For the Q02U/Q03UD/Q04UDH/Q06UDHCPU
Use the Web server module whose serial No.(first five digits) is 09012 or
later.
6 For the Q02PH/Q06PHCPU and Q13UDH/Q26UDH/Q03UDE/Q04UDEH/
Q06UDEH/Q13UDEH/Q26UDEHCPU
Use the Web server module whose serial No.(first five digits) is 10012 or
later.
7 GX RemoteService-I cannot be used.
If it is used for a redundant CPU or Universal model CPU, it does not
function normally.
POINT
Use a Web server module appropriate to each CPU module.
If an unsupported one is used for a CPU module, it does not function normally.
(b) When mounting to remote I/O station of MELSECNET/H
The Web server module cannot be mounted to remote I/O station of the
MELSECNET/H.
Mount it next to the CPU module on the master station.
(From the preceding page)
Base unit (*2)
No. of modules
(*1)
Main base unit
64
N/A
N/A
MELSEC-Q
Extension base
unit
: Applicable,
: N/A
2 - 2