6 FUNCTIONS
6 - 34
(e)
Display form
1)
Set the display form of the real number.
Decimal/Exponential
2)
Set the number of decimal places. (0 to 6)
3)
Enabled when the data type is either of the following.
• Real number type
• Single word/Double word (After operation, a numeric value below
decimal point may be produced.)
(f)
Operator
Set a mathematical operation to be performed for the collected data, or no
mathematical operation to be performed.
(None, +, -,
(g)
Operand
Set the numeric value to be mathematically operated for the collected data.
(-38768 to 32767)
POINT
(1) When collecting multiple device data of the same programmable controller
CPU, registering them as the components of the same tag will make the
collecting operation more efficient than registering them to different tags.
(2) After changing the settings, make sure to click on the "Save" button.
The settings are updated when the "Update" button on the Setting update
screen is clicked, the programmable controller is powered off and then on, or
the CPU module is reset.
REMARKS
(1) How to create user setting system area
The following provides how to create a user setting system area in the program
memory of the control CPU.
[Start Procedure]
GX Developer
[Operation Procedure]
1) Select "Create a user setting system area" as the Format Type on the
Format PLC memory screen.
2) Secure 1K step of "High speed monitor area from other station" for each
Web server module. ( 1)
3) Format the PLC memory.
, / )
[Online]
"Format PLC memory"
MELSEC-Q
1 The area size of 1K step is required
per Web server module separately
from the area used for GX Developer
and/or GOT.
6 - 34