Mitsubishi MELSEC-Q Series User Manual page 163

Web server module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

4 SET-UP AND PROCEDURE BEFORE OPERATION
b15
Logging monitor setting
0: Not display the latest file update time.
1: Displays the latest file update time.
Battery error detection setting
0: Detects battery error.
1: Not detect battery error.
A switch setting error (0180h) will occur during hardware
test if this area is other than 0.
4 - 46
(2) Default operation setting/Battery error detection setting/Logging
monitor setting (switch 2)
Select the default operation setting/battery error detection setting/logging monitor
setting for the Web server module.
to
Speccify 0.
(a)
Default operation setting (bit 0, 1)
For the account setting, system setting and IP filter setting, whether the
default setting is enabled or not is set in this setting.
1)
Account setting (bit 0)
0 : Operates according to the account setting.
1 : Operates according to the default setting.
2)
System setting and IP filter setting (bit 1)
0 : Operates according to the system setting/IP filter setting.
1 : Operates according to the default setting.
POINT
Use the default setting when changing the setting of the Web server module
connected with the personal computer on a one-to-one basis.
b5
b4
b3
b2
b1
b0
0
MELSEC-Q
Switch2
Default operation setting (Account setting)
0: Operates according to the account setting.
1: Operates according to the default setting.
User name : QJ71WS96
Password : MITSUBISHI
Access authority :
Device write/Tag component write/
Administrator
Initial screen :
Standard screen top page
Default operation setting (System setting)
0: Operates according to the system setting.
1: Operates according to the default system
setting.
IP address
: 192.168.3.3
Subnet mask
: 255.255.255.0
Connecting through LAN or the router.
Use the default HTTP port number (80).
Use the default FTP port number (21).
System name : QJ71WS96
Does not execute network diagnoses (Ping).
Automatic connection to network at start-up.
Default operation setting (IP filter setting)
0: Operates according to the IP filter setting.
1: Operates according to the default IP filter
setting.
The IP packet with no filter setting is
passed. (Without filter setting)
4 - 46

Advertisement

Table of Contents
loading

Table of Contents