10.0
Fieldbus Options Configuration
The 682 can be connected to SCT-2200 Fieldbus options to allow the 682 to communicate with a PLC with the necessary
network protocol. The following sections provide details on Fieldbus communications and describe the procedures required to
configure the available network protocols.
NOTE: The SCT-2200 Fieldbus options must be running firmware version 1.25 or higher to communicate with the 682.
10.1 Fieldbus Option Installation
1. Remove the backplate of the 682
2. Wire an RJ45 to blunt-end cable (not provided) to the J4 connector on the 682 CPU board.
NOTE: Maximum RJ45 cable length is 4,000 ft.
682 J4 Pins
1-3 (Not Used)
3. Connect the other end of the cable to one of the RS-485 RJ45 ports on the SCT-2200 Fieldbus module.
Table 10-1. Available SCT-2200 Fieldbus Options for the 682 Indicator
Part No.
182591
Fieldbus, SCT-2200 EtherNet/IP Module
182592
Fieldbus, SCT-2200 PROFINET Module
212772
Fieldbus, SCT-2200 PROFIBUS DP Module
182596
Fieldbus, SCT-2200 DeviceNet Module
182597
Fieldbus, SCT-2200 CANopen Module
182598
Fieldbus, SCT-2200 EtherCAT Module
196694
Fieldbus, SCT-2200 Modbus TCP Module
(Section 2.3 on page
Table 10-2. Pin Assignments
SCT-2200 Fieldbus
Module RJ45 Pins
6-8 (Not Used)
4 (Z)
5 (B-)
5 (Y)
4 (A+)
–
1-3 (Nut Used)
Figure 10-1. SCT-2200 Fieldbus Module Wiring
Description
5).
Wire Color
–
Blue
White/Blue
–
© Rice Lake Weighing Systems ● All Rights Reserved
Fieldbus Options Configuration
Wire Diagram
–
–
Pin
RJ45 Ports
6-8
Not Used
5
B-
4
A+
1-3
Not Used
73