SRX110 Services Gateway Electrical and Power Requirements

Related
Documentation
Copyright © 2012, Juniper Networks, Inc.
Table 20 on page 41
provides clearance requirements for maintaining optimum airflow
and for facilitating maintenance of the device.

Table 20: Clearance Requirements for the Services Gateway

Location
Front of the chassis
Rear of the chassis
Between the front-mounting
flange and rack or cabinet edge
Between the side of the chassis
and any non-heat-producing
surface such as a wall or
cabinet side
Between the side of the chassis
and devices that have fans or
blowers
SRX110 Services Gateway Description on page 3
General Site Guidelines for Installing the SRX110 Services Gateway on page 38
Site Preparation Checklist for the SRX110 Services Gateway on page 35
SRX110 Services Gateway Cabinet Requirements on page 38
SRX110 Services Gateway Rack Requirements on page 39
You must consider the following factors while planning the electrical wiring and power
availability at your site:
Power specifications and requirements for the device
Electrical wiring guidelines for the device installation site
Power, connection, and power cord specifications for the device
Grounding guidelines and specifications for the device
SRX110 Services Gateway Site Electrical Wiring Guidelines on page 67
Site Preparation Checklist for the SRX110 Services Gateway on page 35
Chapter 6: Preparing the Site for Installation
Recommended
Clearance
Requirement for Clearance
2.5 in. (6.35 cm)
Space for service personnel to
remove and install hardware
components
2.5 in. (6.35 cm)
Space for service personnel to
remove and install hardware
components
2.5 in. (6.35 cm)
Space for cable management and
organization
2.5 in. (6.35 cm)
Space for the cooling system to
function properly and to maintain
unrestricted airflow around the
chassis
2.5 in. (6.35 cm)
Space for the cooling system to
function properly and to maintain
unrestricted airflow around the
chassis
41