Lan Reset Option - Visonic PowerMax10-G2 Installer's Manual

Wireless intrusion and fire alarm system
Hide thumbs Also See for PowerMax10-G2:
Table of Contents

Advertisement

The following LAN messages are reported:
Message
Unit is ok
Test aborted
Comm. loss
Rcvr Ip missing
Cable unplugged
Check lan config
Rcvr#1 UnReach.
Rcvr#2 UnReach.
Rcvr#1 UnReg.
Rcvr#2 UnReg.
Broadband Module timeout
err.
Invalid result

5.1.7 LAN Reset Option

1.
Make sure the system is disarmed and then press the
repeatedly until the PowerMax10-G2 display reads "INSTALLER MODE".
2.
When the PowerMax10-G2 display reads [INSTALLER MODE], press
The screen will now prompt you to enter your installer code.
3.
Enter your Installer Code.
The PowerMax10-G2 display will read [NEW INSTL CODE].
4.
When the PowerMax10-G2 display reads [NEW INSTL CODE] press the
or
button repeatedly until the PowerMax10-G2 display will read
[DIAGNOSTICS].
5.
When the PowerMax10-G2 display reads [DIAGNOSTICS], press the
button.
The PowerMax10-G2 display will read [WL DEVICES].∗
6.
When the PowerMax10-G2 display reads [WL DEVICES], press the
button repeatedly until the PowerMax10-G2 display will read [LAN
RESET OPTION].
When the PowerMax10-G2 display reads [LAN RESET OPTION], press the
7.
button.
I
OK
The PowerMax10-G2 display will read [REBOOT].
8.
To reset the broadband module
9.
Press the
button.
I
OK
The PowerMax10-G2 display will revert to [REBOOT].
To reset all LAN setting definitions (does not reset Monitoring Station IP definitions)
66
Description
Broadband Module is functioning correctly.
The diagnostic test is aborted, as follows:
• AC failure – Broadband Module is set to OFF mode.
• Broadband Module has not completed the power-up procedure. In this case, the
installer should wait a maximum of 30 seconds before re-testing.
The RS-232 serial interface between the Broadband Module and the PowerMax10-G2
failed.
Receivers IP 1 and 2 settings are missing in the PowerMax10-G2.
The Ethernet cable is not connected to the Broadband Module.
This message appears in any of the following cases:
• Incorrect Broadband Module IP has been entered.
• Incorrect subnet mask has been entered.
• Incorrect default gateway has been entered.
• DHCP server failure.
Receiver 1 or 2 is inaccessible, as follows:
• Wrong receiver IP has been entered.
• Receiver failure.
• WAN Network failure.
The PowerMax10-G2 unit is not registered to IP receiver 1 or 2.
Broadband Module does not respond to test result within 70 sec.
Broadband Module responds with a result code that is not recognized by the
PowerMax10-G2.
button
.
I
OK
INSTALLER MODE
ENTER CODE:
NEW INSTL CODE
I
OK
or
LAN RESET OPTION
READY 00:00
I
OK
CODE
or
DIAGNOSTICS
I
OK
WL DEVICES
or
I
OK
REBOOT
I
OK
REBOOT
D-302756