Maintenance; Handling System Troubles - Visonic PowerMax10-G2 Installer's Manual

Wireless intrusion and fire alarm system
Hide thumbs Also See for PowerMax10-G2:
Table of Contents

Advertisement

7. MAINTENANCE

7.1 Handling System Troubles

Fault
1-WAY
NOT NETWORKED
MISSING
JAMMING
LOW BATTERY
CLEAN ME
GAS TROUBLE
SIREN AC FAILURE
AC FAILURE
GSM NET FAIL
RSSI LOW
AC SUPPLY FAILURE
68
What it means
The control panel cannot configure or control
the device.
Battery consumption increases.
A device was not installed or not installed
correctly, or, cannot establish communication
with the control panel after installation.
A device or detector has not reported for some
time to the control panel.
A radio-frequency signal which is blocking
communication channel of sensors and control
panel is detected.
The battery in a sensor, keyfob or wireless
commander is near the end of its useful life.
The fire detector must be cleaned
Gas detector failure
There is no power to the siren
There is no power to gas sensor
The GSM communicator is not able to connect
to the cellular network.
The GSM communicator has detected that GSM
network signal is weak
There is no power and the system is working on
backup battery power
Solution
i) Make sure the device is physically present.
ii) Check the display for device faults, for
example, low battery.
iii) Use RF diagnostics to check the current
signal strength and during the last 24 hours.
iv) Open the device cover and replace the
battery or press the tamper switch.
v) Install the device in a different location.
vi) Replace the device.
i) Make sure the device is physically present.
ii) Use RF diagnostics to check the current
signal strength and during the last 24 hours.
iii) Open the device cover and replace the
battery or press the tamper switch.
iv) Enroll the device again.
i) Make sure the device is physically present.
ii) Check the display for device faults, for
example, low battery.
iii) Use RF diagnostics to check the current
signal strength and during the last 24 hours.
iv) Replace the battery.
v) Replace the device.
Locate the source of interference by switching
off any wireless devices (cordless telephones,
wireless ear plugs, etc.) in the house for 2
minutes then check if trouble continues.
Use also RF diagnostics to check signal
strength.
i) For AC powered devices, check AC power is
available and connected to the device.
ii) Replace the device battery.
Use a vacuum cleaner to clean the detector air
vents occasionally to keep them free of dust.
Gas detector: Disconnect and then put back
the AC power supply connector
CO Gas detector: Replace the detector
Make sure that the AC power supply is
connected properly
Make sure that the AC power supply is
connected properly
i) Move the Panel and GSM unit to another
location.
ii) Enter and exit the installer menu
iii) Disconnect GSM unit and install it again
iv) Replace SIM card
v) Replace the GSM unit
Move the Panel and GSM unit to another
location.
Make sure that the AC power supply is
connected properly
D-302756

Advertisement

Table of Contents
loading

Table of Contents