Physical Properties; Installation; Supplying Power To The Unit; Inserting Backup Battery - Visonic PowerMax10-G2 Installer's Manual

Wireless intrusion and fire alarm system
Hide thumbs Also See for PowerMax10-G2:
Table of Contents

Advertisement

Ring Detection: The unit does not support ring detection
without DC voltage present on the telephone lines.

2.5 Physical Properties

Operating Temp. Range: 14°F to 120°F (-10°C to 49°C)
Storage Temp. Range: -4°F to 140°F (-20°C to 60°C)

3. INSTALLATION

Note: This system must be checked by a qualified
technician at least once every three (3) years.

3.1 Supplying Power to the Unit

Connect power to the PowerMax10-G2 temporarily (see
Figure 3.2). Alternatively, you may power up from the
backup battery, as shown in Figure 3.1.
Disregard any "trouble" indications pertaining to lack of
battery or lack of telephone line connection.
For Europe Safety Compliance:
a. The model shall be installed according to the local
electrical code.
b. The circuit breaker shall be readily accessible.
c. The rating of the external circuit breaker shall be 16A
or less.
d. The cables for the AC mains connection shall have an
overall diameter of 13mm and 16mm conduit.
Please refer to Figure 3.2 "Power Cable Connection".

3.1.1 Inserting Backup Battery

Connect battery pack as shown in the next drawing.
1. Battery insertion
2. Battery connection
Figure 3.1 – Connecting Battery

3.1.3 Telephone Wiring

Connect the telephone cable to the SET connector and connect the telephone line cable to the LINE connector (through
4
1
2
PHONE WIRING
the desired wiring cable entry).
Humidity: 85% relative humidity, @ 30°C (86°F)
Size: 193 x 178 x 50 mm (7-5/8 x 7 x 2 in.)
Weight: 658g (23 Oz) (with battery)
Color: White

3.1.2 Connecting Power to Panel

Connect the power cable and close the control panel as
shown below. Electrical socket-outlet shall be installed
near the equipment and shall be easily accessible.
WARNING!
DO NOT USE AN OUTLET CONTROLLED
BY A WALL SWITCH.
Note: This equipment should be installed in accordance with
Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72,
(National Fire Protection Association).
Connect the power adapter to the power connector.
Fig. 3.2 - Power Cable Connection
D-302756

Advertisement

Table of Contents
loading

Table of Contents