Status Area and Troubleshooting

10-2 Status Area and Troubleshooting

10-2-1 CS-series Controller Link Units

Status Area
Error Information: CIO 1500 + 25 x (Unit No.)
Polling Node Address, Startup Node Address: CIO 1500 + 25 x (Unit No.) + 1
Note Stop the data link from the node at which the LNK indicator is lit (indicating
active data links). Data links cannot be stopped from nodes which do not have
active data links.
The status of the Unit and the communications status of the Controller Link
Unit is recorded in the Status Area of the PLC. The cause of errors can be
found by searching the Status Area. The Status Area can be read using a Pro-
gramming Console, the SYSMAC Support Software, or the Controller Link
Support Software.
This section explains the contents of the Status Area and tells how to trouble-
shoot errors recorded there.
The status of the Unit and Network is indicated in the following manner in the
PLC.
Status information related to duplex operation of Communications Units is
reflected in the PLC's Auxiliary Area. For details, refer to 10-1 Troubleshooting
Using Indicators and Auxiliary Area on page 259.
1: Network parameter error (in PLC's EEPROM)
1: Data link table error (in PLC's EEPROM)
1: Routing table error (in PLC's EEPROM)
1: PLC system setting error
1: EEPROM error
1: Duplicate node address setting error
1: Inconsistent network parameters
1: Communications controller send error
1: Communications controller hardware error
1: Error log exists
Polling node address
Startup node address
Each node address is displayed in 2-digit BCD.
Section 10-2
213