Omron CS1W-CLK12-V1 Operation Manual page 246

Optical ring controller link units
Hide thumbs Also See for CS1W-CLK12-V1:
Table of Contents

Advertisement

Error Log
Error
Contents
code
0109
Transmission failed; destination
Hex
busy
010A
Transmission failed; communica-
Hex
tions controller error
010B
Transmission failed; PLC error
Hex
010C
Transmission failed; unit number
Hex
incorrect
010D
Transmission failed; destination
Hex
address incorrect
010E
Transmission failed; routing
Hex
tables not registered
010F
Transmission failed; routing table
Hex
error
0110
Transmission failed; too many
Hex
relay points
0111
Transmission failed; command
Hex
packet too long
0112
Transmission failed; header
Hex
error.
0113
Transmission failed; I/O setting
Hex
error
0114
Transmission failed; CPU bus
Hex
error
0115
Transmission failed; redundant
Hex
I/O allocations
Detail code
1st byte
2nd byte
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Correction
Written to
EEPROM
Increase number of
No
retries or reconfig-
ure system to distrib-
ute load.
Conduct an echo-
Yes
back test and if the
effects of noise are
considerable, recon-
sider the operating
environment. Restart
the Controller Link
Unit. If the error
occurs again,
replace the Unit.
Refer to the PLC
No
operating manual. If
the error occurs
again, replace the
PLC.
Check unit number
No
settings to be sure
they are within range
and unique.
Refer to 7-4 Setting
No
Routing Tables, and
set a destination
address in the rout-
ing table.
Refer to 7-4 Setting
No
Routing Tables, and
set a routing table for
the source node,
destination node,
and relay node.
Refer to 7-4 Setting
No
Routing Tables, and
correctly set the rout-
ing table.
Check routing tables
No
and system configu-
ration. Do not try to
access Networks
separated by more
than one other Net-
work.
Be sure to use the
No
FINS command for-
mat.
Be sure to use the
No
correct FINS com-
mand format.
Check I/O table
No
accuracy.
Check Unit and cable
No
connections and
clear error.
Check unit numbers
No
for redundancy
within the same PLC.
Section 10-3
Applicable
PLC
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
CV, CS
229