Omron CS1W-CLK12-V1 Operation Manual page 229

Optical ring controller link units
Hide thumbs Also See for CS1W-CLK12-V1:
Table of Contents

Advertisement

Troubleshooting Using Indicators
Node Cannot Participate
in Data Link
Data Link Cannot be
Stopped
212
Indicators
LNK
M/A
Lit
---
Data link operating normally.
Flashing ---
There is an error in the data
link tables.
When manual setting is used,
either data link tables have not
been created for the startup
node or there is an error in the
data link tables.
When automatic setting is
used, either the data link
parameters for the startup
node have not been set or
there is an error in the data
link tables.
Not lit
Lit
Manually set data links are
already operating on the same
Network.
Not lit
Not lit
Automatically set data links
are already operating on the
same Network.
There is an error in the startup
node PLC.
The following table describes the LNK and M/A indicators when a node can-
not participate in the data links.
Data link participation depends on the Controller Link Unit operating normally
and participating in the Network. Refer to Troubleshooting with RUN, ERC,
ERH and INS Indicators earlier in this section and check Unit operation before
using the following table.
Indicators
LNK
M/A
Lit
---
Data link operating normally.
Flashing Lit
When manual setting is used,
there is an error in the data
link table.
Flashing Not lit
When automatic setting is
used, the data link parameters
at the startup node are incor-
rect for the local node (the
data link area is out of range
for the local node.)
Not lit
Lit
When manual setting is used,
there are no data link tables
set for the local node.
Not lit
Not lit
When automatic setting is
used, the startup node is not
set to participate in the data
links.
Stopping the data link depends on the Controller Link Unit operating normally
and participating in the Network. Read the above explanations before
attempting to stop operation.
Probable cause
---
When the ERH indicator is
flashing, remake and set the
data link tables.
Refer to 5-2-2 Manual Setting
and set data link tables for the
startup node.
Refer to 5-2-4 Automatic Set-
ting: Select All and set the
automatic parameters for
starting the data links.
Stop the manually set data
links that are operating and
restart the data links.
Stop the automatically set
data links that are operating
and restart the data links.
Refer to the PLC's operation
manual and correct the error.
If the error reoccurs, replace
the PLC.
Probable cause
---
Refer to 5-2-2 Manual Setting
and remake the data link table.
Refer to 5-2-4 Automatic Set-
ting: Select All, reset the
parameters for the startup
node DM Area so that the
local node can participate in
the data link, and then restart
the data link.
Set data link tables for the
local node.
Stop the data links, remake
and set the parameters in the
startup node's DM Area, and
then restart the data link.
Section 10-1
Probable remedy
Probable remedy