Omron CS1W-CLK12-V1 Operation Manual page 64

Optical ring controller link units
Hide thumbs Also See for CS1W-CLK12-V1:
Table of Contents

Advertisement

Component Names and Functions
Meanings of LED
Indicators
Name
RUN
Green
(operating)
P/S
Green
(power supply)
ERC (communica-
Red
tions error)
ERH
Red
(PLC error)
INS
Yellow
(network participa-
tion)
SD
Yellow
(send)
RD
Yellow
(receive)
M/A
Yellow
(data link mode)
LNK
Yellow
(data link)
RING
Yellow
(transmission path
format)
Note Even when the local node does not participate in the data link, the
indicator will be lit if there are manually set data links active on the
network.
For details refer to 10-1 Troubleshooting Using Indicators.
Note The INS, SD, RD, M/A, LNK, and RING LED indicators on Controller Link
Units in standby mode are not lit.
Color
Status
Lit
Unit operating normally or, if Communica-
tions Units are used in duplex operation, Unit
operating normally in active mode.
Flashing
If Communications Units are used in duplex
operation, Unit operating normally in standby
mode.
Not lit
Unit error.
Lit
Backup power is being supplied.
Not lit
Backup power is not being supplied.
Lit
Communications error, node address setting
error, hardware error or a connection error
between the Optical Controller Link Unit and
SYSMAC LINK.
Not lit
Normal operation
Lit
PLC error, PLC interface error, EEPROM
error, unit number error, I/O table not set,
duplex communications setting error, or
duplex settings incomplete
Not lit
No error.
Lit
Unit is participating (inserted) in the network.
Not lit
Unit is not participating (inserted) in the net-
work.
Lit
Data transmission.
Not lit
No data transmission.
Lit
Data reception.
Not lit
No data reception.
Data
links
active in
the net-
work.
Lit
Manual
(See
note.)
Not lit
Auto-
matic
Lit
Data links participating.
Flashing
Error in data link table.
Not lit
Not in a data link or data link inactive.
Lit
Token-ring mode setting (cable normal)
Flashing
Token-ring mode setting (cable discon-
nected)
Not lit
Token-bus mode setting
Section 3-1
Meaning
Data links not active in the net-
work.
Note:
M/A is always not lit when data
links are not active in the network.
47