Using the Message Service
PLC Programming Examples
CS-series PLCs
Execution
condition
000000
A20207
120002
(See note 1.)
120001
120000
(See note 1.)
120000
A20207
Network Instruction Error Flag
120000
A21907
(Continued on the next page)
The transmission program will run when CIO 00000
KEEP
120000
turns ON, provided that the Network Instruction En-
S
abled Flag is ON and the RECV instruction has not
been executed.
R
CIO 120000 remains ON while the SEND instruction
is being executed, and it turns OFF when instruction
@MOV(21)
execution has been completed.
#000A
Control Data Preparation
D00000
Word
@MOV(21)
D00000
#0002
D00001
D00001
D00002
@MOV(21)
#0400
D00002
D00003
@MOV(21)
#0705
D00003
D00004
@MOV(21)
#0064
D00004
Transfers the 10 words beginning at CIO 0000 to the
@XFER(70)
10 words beginning at D00010.
#000A
0000
D00010
Transfers the 10 words beginning at DM 00010 of
@SEND(90)
the local node to the words beginning with D00020
D00010
at network address 2, node address 4, and Unit
D00020
address 0 (PLC).
D00000
DIFU(13) 120001
Creates reset input.
Turns ON to indicate transmission error.
121000
Section 6-3
Content
Meaning
0 0
0 A 10 send words
0 0
0 2
Destination network
address= 2
0 4
0 0
Remote node
address = 4
Destination Unit
address = 0
0 7
0 5
Response required
Port No. 7 used
No. of resends = 5
0 0
6 4
Response monitoring
time = 10 s