Setting The Unit Number - Omron CS1W-CLK12-V1 Operation Manual

Optical ring controller link units
Hide thumbs Also See for CS1W-CLK12-V1:
Table of Contents

Advertisement

CS-series Optical Ring Controller Link Units
4-1-2

Setting the Unit Number

Transmission Path Format Setting (Software Switch)
Setting range
Token-ring mode
Token-bus mode
Software switch (DM30000 + 100 x unit number)
0: Always set to 0.
-: Other settings.
Transmission Path
9
0
0
1
1
Set the unit number for each Unit using the rotary switches on the front of the
Unit. When using Controller Link Units in duplex operation, set the same unit
number for each active/standby pair of Units. The unit number is used to iden-
tify a CPU Bus Unit in the PLC. Any unit number can be set between 0 and F
in hexadecimal (00 to 15 in decimal).
Item
Setting method
Setting range
Node
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
Note
1. Always turn OFF the PLC's power before setting the unit number.
2. When setting a Unit for the first time or changing the existing setting, create
a I/O table in the PLC's CPU Unit.
3. If there are no Units used in duplex operation, do not set the same unit
number twice within the same PLC. An error will occur if the same unit
number is set for two different Units, and the CPU Unit will not be able to
recognize the Units. If there are Units used in duplex operation, they will be
recognized when the duplex settings have are made and the I/O tables rec-
reated.
4. When there are Controller Link Units used in duplex operation, if different
unit numbers are set for an active/standby pair of Units, they will not be rec-
ognized as a pair, and will not operate properly.
5. When the Unit is recognized by the PLC's CPU Unit, "Controller Link Unit
(NS)" will be shown in the I/O table displayed at the CX-Programmer.
6. The default setting is "0."
7. The unit number determines the DM parameter area used by the Controller
Link Unit in PLC memory.
All nodes in the Network
Transmission path setting
Bit
8
0
Token-ring mode
1
0
1
Token-bus mode
0
0
Note: The factory default settings are shown above.
Single-digit hexadecimal
0 to F (decimal 00 to 15, default is 0)
All nodes in the Network
Section 4-1
Nodes
Setting contents
Specifications
67