Omron CS1W-CLK12-V1 Operation Manual page 244

Optical ring controller link units
Hide thumbs Also See for CS1W-CLK12-V1:
Table of Contents

Advertisement

Error Log
Error
Contents
code
0003
PLC shared RAM error
Hex
0004
CPU Bus Unit ID number error
Hex
0005
Unit number error
Hex
0006
CPU Unit error
Hex
000E
I/O Bus error
Hex
000F
PLC initialization error
Hex
0010
PLC Setup exceeds capacity
Hex
0011
PLC initialization error
Hex
(Time out)
0012
CPU Unit memory error
Hex
0013
CPU Unit write-protected
Hex
Detail code
1st byte
2nd byte
01 Hex:
00 Hex
Cyclic
02 Hex:
Event
04 Hex:
CPU bus link
00 Hex
00 Hex
Unit set
The value
value
recognized
by the CPU
Unit
Bit 11: No relevant Unit in
I/O table.
Bit 12: Hardware test unit
number recog-
nized.
Bit 13: Incorrect unit num-
ber.
Bit 14: Duplicated unit
number.
00 Hex fixed 00 Hex fixed Check the operating
01 Hex:
01 Hex:
Read error
Data link
02 Hex:
table
Write error
02 Hex: Net-
work param-
eters
03 Hex:
Routing
table
04 Hex: PLC
Setup Area
Correction
Written to
EEPROM
Check operating
Yes
environment.
Check I/O Connect-
Yes
ing Cables.
Check the Unit num-
Yes
ber setting. Recre-
ate the I/O table.
Check the Unit num-
Yes
ber settings. Recre-
ate the I/O table.
Yes
environment.
Check the operating
Yes
environment.
Reduce the number
Yes
of CPU Bus Units
mounted on each
CPU Unit by one.
Check the operating
Yes
environment.
Reset the appropri-
Yes
ate data.
Release the CPU
Yes
Unit write protect.
Section 10-3
Applicable
PLC
CV
CV, CS
CV
CV, CS
CS
CS
CS
CS
CS
CS
227