Response Codes
Main code
04: Not executable
05: Routing error
10: Command format
error
11: Parameter error
Sub-
Probable cause
code
01
An undefined command has been
used.
02
Cannot process command because the
specified unit model or version is
wrong.
01
Remote node address is not set in the
routing table.
02
Routing table isn't registered.
03
Routing table error
04
The maximum number of relay nodes
(2) was exceeded in the command.
01
The command is longer than the max.
permissible length.
02
The command is shorter than min. per-
missible length.
03
The designated number of data items
differs from the actual number.
04
An incorrect command format has
been used.
05
An incorrect header has been used.
(The local node's relay table or relay
node's local network table is wrong.)
01
A correct memory area code has not
been used or Extended Data Memory
is not available.
02
The access size specified in the com-
mand is wrong, or the first address is
an odd number.
03
The first address is in an inaccessible
area.
04
The end of specified word range
exceeds the acceptable range.
The total number of words exceeds the
acceptable range.
06
A non-existent program no. has been
specified.
09
The sizes of data items in the com-
mand block are wrong.
A node that is not set as a common link
parameter is in the refresh parameters.
0A
The IOM break function cannot be exe-
cuted because it is already being exe-
cuted.
There are node addresses that have
been set twice.
0B
The response block is longer than the
max. permissible length.
0C
An incorrect parameter code has been
specified.
There is a file error.
Remedy
Check the command code and be sure that
the Unit supports it.
Check the unit model and version.
Set the remote node address in the routing
table.
Set the local nodes, remote nodes, and
relay nodes in the routing table.
Set the routing table correctly.
Redesign the network or reconsider the
routing table to reduce the number of relay
nodes in the command.
Check the command format of the com-
mand and set it correctly.
Check the command format of the com-
mand and set it correctly.
Check the number of items and the data,
and make sure that they agree.
Check the command format of the com-
mand and set it correctly.
Set the routing table correctly.
Check the command's memory area code
and set the appropriate code.
Set the correct access size for the com-
mand.
Set a first address that is in an accessible
area.
Check the acceptable limits of the data area
and set the word range within the limits.
Check the data link tables to be sure the
limit to link words has not been exceeded.
Check the program number and be sure
that it is set correctly.
Check the command data and be sure that
the sixes of the data items are correct.
Check the data link tables to be sure all
nodes in the refresh parameters are in the
common link parameters.
Either abort the current IOM break function
processing, or wait until it is completed and
execute the command.
Check the data link tables for node
addresses that have been set twice.
Check the command format and set the
number of items correctly.
Check the command data and reenter it cor-
rectly.
Check the data link table file for corruption.
Section 6-6
147