Omron CS1W-CLK12-V1 Operation Manual page 269

Optical ring controller link units
Hide thumbs Also See for CS1W-CLK12-V1:
Table of Contents

Advertisement

Handling Precautions
Continuing Operation in
Token-bus Mode
1,2,3...
Changing Operation to
Token-ring Mode
1,2,3...
Resetting Network Parameters
1,2,3...
252
0: Always set to 0
-: Other settings
Transmission Path
Bit
9
0
0
0
1
1
0
1
1
The Optical Bus and Optical Ring Controller Link Units can be used together if
you want to keep the system in token-bus mode (daisy-chain connections).
Some of the Optical Bus Controller Link Units in the system can be replaced
with Optical Ring Controller Link Units that use H-PCF cable.
1. Replace the Unit and turn the power ON without the optical fiber cable con-
nected.
2. Set the transmission format for the replaced Unit to "token-bus mode" with
bits 8 and 9 of D30000 + (100 × unit number).
3. Turn the power OFF and then ON again and verify that the Controller Link
Unit's RING indicator is not lit. (The Unit is set to token-bus mode if the
RING indicator is not lit.)
4. Leave the cable disconnected and set the network parameters. See "Re-
setting Network Parameters" below for details.
5. Turn the power OFF and install the network cable connector.
6. Check the connections, turn the power ON to all of the nodes, verify that
the INS indicators are lit, and verify that the network has started operating
normally.
If all of the Controller Link Units in the network are Optical Ring Controller Link
Units (using H-PCF cable), the network can operate in token-ring mode. All of
the nodes in the network must be set to token-ring mode.
1. Replace the Unit and turn the power ON without the optical fiber cable con-
nected.
2. Set the transmission format for the replaced Unit to "token-ring mode" with
bits 8 and 9 of D30000 + (100 × unit number).
3. Turn the power OFF and then ON again and verify that the Controller Link
Unit's RING indicator is lit. (The Unit is set to token-ring mode if the RING
indicator is lit.)
4. Turn the power OFF and install the optical fiber cable connector. Connect
the nodes at the ends of the network to form a ring configuration.
5. Check the connections, turn the power ON to all of the nodes, verify that
the INS indicators are lit, and verify that the network has started operating
normally.
When a CPU Unit has been replaced for a CVM1 or CV-series Controller Link
Unit, it is necessary to reset the network parameters, data link tables, and
routing tables. This sections describes the resetting procedure for the network
parameters. For details on data link table resetting procedures, refer to 5-2
Setting Data Links and for routing table resetting procedures, refer to 7-4 Set-
ting Routing Tables.
1. Network parameters are read from the polling node when the Network is
activated and this information is distributed to all nodes in the Network. For
Transmission format
8
Token-ring mode
Token-bus mode
Section 10-7
Setting