Applicable Cable; Termination Of Cable End; Removal And Installation Of Can Bus Connector - Mitsubishi Electric MELSEC-F FX3U-CAN User Manual

Hide thumbs Also See for MELSEC-F FX3U-CAN:
Table of Contents

Advertisement

FX
-CAN User's Manual
3U
4.1.2

Applicable cable

Item
Cable Type
Unshielded/ Shielded
No. of Pairs
Conformance Standard
Wire Size
Impedance
Note
The bus length, length related resistance and the cross section of the cable to be used should be related as
follows.
Guidelines for the cable are available in CiA
Bus Length (m)
0 to 40
40 to 300
300 to 600
600 to 1000
4.1.3

Termination of cable end

Strip 9 mm (0.35") of insulation from the end of the wire. For stranded wires, terminate the
end of the wire using a wire ferrule with insulating sleeve.
Tighten the terminals to a torque of 0.4 to 0.5 N • m.
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to
do so may cause equipment failures or malfunctions.
• When using stranded wires
It may be difficult to insert the electric wire into the insulating sleeve
depending on the thickness of the electric wire sheath. Select
appropriate electric wire by referring to the dimensions of the wire
ferrule.
<Reference>
Manufacturer
Phoenix Contact
*1. Old model name : CRIMPFOX ZA 3
*2. Old model name : CRIMPFOX UD 6
4.1.4

Removal and installation of CAN bus connector

1) Removal
Evenly unscrew both CAN connector mounting screws, and remove the CAN connector from the module.
If the cable is attached to the connector, hold and pull the connector on the side. Do not pull the cable.
2) Installation
Place the CAN connector in the specified position, and evenly tighten both CAN connector mounting
screws.
Tightening torque 0.4 to 0.5 N • m
Do not tighten the terminal block mounting screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
30
Applicable Cable
Twisted pair cable
ISO 11898/1993
2
0.3 mm
to 0.82 mm
Length Related Resistance (mΩ/m)
70
Less than 60
Less than 40
Less than 26
Model names
AI 0.5-8WH
AI-TWIN 2X 0.5-8WH
Shielded
2 pair
2
(AWG22 to 18)
120 Ω
®
303.
Cross Section (mm
0.3 to 0.34 (AWG 22)
0.34 to 0.60 (AWG 22 to 19)
0.50 to 0.60 (AWG 20 to 19)
0.75 to 0.80 (AWG 18)
Caulking tool
*1
CRIMPFOX 6
*2
(or CRIMPFOX 6T-F
)
4.1 Applicable Cable and Connector
→ For details, refer to CiA
2
)
Insulating sleeve
2.6mm
(0.11")
14mm(0.56")
4 Wiring
®
303
9mm
(0.35")
Contact area
(Crimp area)
8mm
(0.32")

Advertisement