Siemens SIMATIC ET 200AL System Manual page 1201

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Communications services
3.6 Secure Communication
5. Create one of the instructions TSEND_C, TRCV_C or TCON in the program editor.
6. Interconnect the CONNECT parameter of one of the instructions TSEND_C, TRCV_C or TCON
with the tags of the data type TCON_IP_V4_SEC.
Settings at the TLS server
To set up a secure TCP connection in the TLS server, follow these steps:
1. Create a global data block in the project tree.
2. Define a tag of the data type TCON_IP_4_SEC in the global data block.
The example below shows the global data block "Data_block_1" in which the tag "SEC
connection 1 TLS-Server" of the data type TCON_IP_V4_SEC is defined.
Figure 3-26
IP_V4_SEC_Server
3. Set the connection parameters of the TCP connection in the "Start value" column. For
example, enter the IPv4 address of the TLS client for "RemoteAddress".
4. Set the parameters for secure communication in the "Start value" column.
– "ActivateSecureConn": Activation of secure communication for this connection. If this
– "TLSServerReqClientCert ": Request for an X.509-V3 certificate from the TLS client.
– "TLSServerCertRef": ID of the own X.509-V3 certificate.
– "TLSClientCertRef": Enter the value 2 (reference to the CA certificate of the TIA Portal
80
parameter has the value FALSE, the subsequent security parameters are irrelevant. You
can set up a non-secure TCP or UDP connection in this case.
Enter the value "true".
project (SHA256) or the value 1 (reference to the CA certificate of the TIA Portal project
(SHA1)). If you use a different CA certificate, enter the corresponding ID from the
certificate manager of the global security settings.
Function Manual, 05/2021, A5E03735815-AJ
Communication

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents