Rules For The Replacement Parts Scenario - Siemens SIMATIC ET 200AL System Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Communications services
3.6 Secure Communication
3.6.2.8

Rules for the replacement parts scenario

The assignment of passwords to protect confidential PLC configuration data also has an
impact on the replacement parts scenario.
Rules for the replacement parts scenario
Observe the following rules for the replacement parts scenario:
Configuration of the replacement CPU via TIA Portal
• A CPU as replacement for an existing CPU should not have a configuration or a configured
password to protect confidential PLC configuration data.
Advantage: You can load the project into the replacement CPU without any further
preparation - regardless of whether a password is configured or not.
• If the replacement CPU has already been configured, you must reset the CPU to the factory
settings with the following options set:
– "Delete password for protection of confidential PLC configuration data"
– "Format memory card"
Replacement CPU is supplied with configuration data via memory card
• If you have not assigned a password to a CPU in your project to protect confidential PLC
configuration data, you can insert the memory card of the CPU to be replaced into a
brand-new, unused CPU without any further action needed.
If the replacement CPU has already been configured with a password to protect
confidential PLC configuration data, you must first reset this CPU to the factory settings
using the option "Delete password for protection of confidential PLC configuration data".
• If you have assigned the same password to a group of CPUs, you can also assign the group
password to the replacement CPU via the TIA Portal or via an appropriately prepared
memory card (see Protection of confidential configuration data (Page 61)).
In this case you can, for example, insert a memory card with the current project into the
CPU and put it into operation without any further password handling.
• If you assign different passwords to each CPU in your project, you must first set the
password valid for the respective CPU with the online and diagnostics editor when using
the replacement CPU (area "Set password for protection of confidential PLC configuration
data", see Changing your password (Page 65)).
See also
Assign password via SIMATIC Memory Card (Page 68)